2021 IBC Chapter 1

Lesson 1: Administration: Permits, Documents, and Inspections

IBC 101 to 116 · 14 practice questions

0:00 / --:--

Reading

Chapter 1 of the IBC does not tell anyone how to build a wall. It tells everyone who decides, what needs a permit, what has to be drawn, when the building official comes out, and what piece of paper lets people use the building. On a community clinic, a small apartment building, or a church fellowship hall, most of the surprises come from this chapter, not from the structural or fire chapters. This lesson walks a project from application to certificate of occupancy, then covers what happens when something goes wrong.

From permit application to certificate of occupancy A flow chart. An application leads to plan review and then a permit. Required inspections follow: footing and foundation, slab and under-floor, frame, lath and gypsum board, and fire and smoke penetrations, plus lowest floor elevation, Type IV connection protection, balcony waterproofing, energy and special inspections when they apply. The final inspection leads to the certificate of occupancy. 1 Application 105.3, 107: forms and drawings 2 Plan review 107.3, 105.3.1: documents checked 3 Permit issued 105.3.1, 105.7: placed on the site Inspections the permit holder calls in (110.3, 110.5). No work goes past a failed point until approved (110.6). Footing and foundation 110.3.1 Slab and under-floor 110.3.2 Frame 110.3.4 Lath and gypsum board 110.3.6 Fire and smoke penetrations 110.3.8 Also, as the project calls for them Lowest floor flood areas 110.3.3 Connections Types IV 110.3.5 Balcony seal waterproofing 110.3.7 Energy 110.3.9 Special inspections 110.3.11 Final inspection 110.3.12 all permit work complete Certificate of occupancy 111 required before use or a change of use
The path every permitted job follows. The inspection boxes are listed by section number, not in strict job order: the order on site follows the work.

Scope, purpose, and where existing buildings go

Section 101 sets the scope: the IBC governs the construction, alteration, repair, and use of buildings and structures. Section 101.4 lists the companion codes, and 101.4.7 sends repair, alteration, change of occupancy, addition, and relocation of existing buildings to the International Existing Building Code. That pointer matters for GCHS, because most rehab work is on existing buildings. This course teaches the new-construction provisions of the IBC; the existing-building code decides how much of them an older building must meet. Section 102.6 adds that the legal occupancy of a structure that existed on the date of adoption may continue without change, except where the codes say otherwise. Chapter 2 holds the definitions, including fire area, occupant load, high-rise building, and change of occupancy.

Which edition applies: Texas and Houston

This course teaches the text of the 2021 IBC. Which edition actually binds a project depends on local adoption. As checked on September 28, 2026: Texas Local Government Code Section 214.216 makes the IBC as it existed on May 1, 2012 the default municipal commercial building code (House Bill 738 of 2021 moved that date forward from May 1, 2003, effective January 1, 2022). That is a floor, and cities may adopt newer editions by ordinance. The City of Houston approved the 2021 I-Codes, with local amendments, on October 25, 2023, effective January 2, 2024. Only projects submitted after that date follow them; earlier applications stay under the 2015 Construction Code. So never say that Texas uses the 2021 IBC. Ask the jurisdiction which edition and which amendments apply. The edition used for the permit is printed on the certificate of occupancy (111.2).

When a permit is required

Section 105.1 says an owner or the owner's authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure, or to install regulated electrical, gas, mechanical, or plumbing systems, must first apply to the building official and obtain the permit. Note that changing the occupancy is on the list even when no wall moves. Section 105.2 then lists work exempt from a permit. Its lead-in carries a warning: an exemption is not authorization to violate the code. Local amendments often change the list, so check the adopted version.

Key numbers
  • Shed or playhouse: one-story detached accessory, floor area not greater than 120 sq ft (105.2)
  • Fences not over 7 ft; window awnings in R-3 and U projecting not more than 54 in. with no added support
  • Retaining walls not over 4 ft, measured from the bottom of the footing to the top of the wall, unless supporting a surcharge or impounding Class I, II, or IIIA liquids
  • Sidewalks and driveways not more than 30 in. above adjacent grade, not over a basement or story below, and not part of an accessible route
  • Painting, papering, tiling, carpeting, cabinets, counter tops, and similar finish work; nonfixed movable fixtures, cases, racks, counters, and partitions not over 5 ft 9 in.
  • Application deemed abandoned 180 days after filing; extensions up to 90 days each (105.3.2)
  • Permit invalid if work does not start within 180 days of issue or stops for 180 days; extensions up to 180 days each, in writing (105.5)

Applications, and how long a permit lasts

Under 105.3.2 an application is deemed abandoned 180 days after filing unless the applicant is pursuing it in good faith or a permit has been issued. The building official may grant extensions of not more than 90 days each, requested in writing with justifiable cause. Once issued, a permit becomes invalid under 105.5 if the work does not commence within 180 days, or if the work is suspended or abandoned for 180 days after it starts. Extensions must be requested in writing, with justifiable cause, and each is limited to 180 days. Temporary structures and uses (Section 108) are allowed for not more than 180 days, with extensions for demonstrated cause.

Worked example. A fellowship hall addition is filed on March 1, 2027 and the design team goes quiet. Counting 180 days gives August 28, 2027, the date the application is deemed abandoned unless it is being pursued in good faith. Suppose the permit is issued September 1, 2027, the foundation starts September 20, and the church stops work on October 15 for lack of funds. Another 180 days gives April 12, 2028. If work is still suspended on that date, the permit is invalid unless a written extension was granted. The official's counting practice governs the exact day, so treat these as planning dates and call early.

Construction documents

Section 107.1 requires construction documents, the statement of special inspections, the geotechnical report, and other data in two or more sets (or digitally where the jurisdiction allows). The documents are prepared by a registered design professional where required by the statutes of the jurisdiction; the IBC itself does not always require one, and the Texas engineering and architectural practice acts decide when a licensed professional is needed. The official may waive submittal where a review is not necessary. Section 107.2 lists what the documents must show, including fire protection shop drawings (107.2.2), the means of egress (107.2.3), the exterior wall envelope (107.2.4), details of the moisture barrier system for exterior balconies and elevated walking surfaces (107.2.5), the site plan (107.2.6), and structural information (107.2.7). Amended documents go back for approval (107.4).

Required inspections

Section 110.1 puts the burden on the owner or agent to keep work visible and accessible until it is approved, and it says that an approved inspection is never approval of a violation. Section 110.2 lets the official examine the site before issuing a permit. Section 110.3 lists twelve inspection items, 110.3.1 through 110.3.12. The permit holder notifies the official when work is ready (110.5), and work may not go past an inspection point without approval; portions that fail must be corrected and stay uncovered until authorized (110.6). The official may accept reports of approved inspection agencies (110.4).

InspectionSectionMade when
Footing and foundation110.3.1Excavation done, reinforcing and forms in place
Slab and under-floor110.3.2Reinforcing and under-slab services in place, before concrete or floor sheathing
Lowest floor elevation110.3.3Flood hazard areas
Frame110.3.4Roof deck, framing, fireblocking, and bracing in place; rough electrical, plumbing, and mechanical approved
Types IV-A, IV-B, IV-C connection protection110.3.5Wood cover inspected before other coverings (new in 2021)
Lath and gypsum board110.3.6Before plaster or before taping and finishing
Balcony and walking surface waterproofing110.3.7Before the moisture barrier is concealed
Fire and smoke penetrations110.3.8Before they are concealed
Energy, other, and special inspections110.3.9 to 110.3.11As the project requires
Final110.3.12All permit work complete; flood hazard elevation documents in first (110.3.12.1)

Certificate of occupancy

Section 111.1 says no building may be used or occupied, and no change of occupancy made, until the building official issues a certificate of occupancy. Under 111.2 the certificate is issued after an inspection finds no violations, and it lists twelve things: the permit number, the address, the owner's name and address, a description of the portion covered, a statement that it was inspected for compliance, the building official's name, the code edition used for the permit, the use and occupancy group (Chapter 3), the type of construction (Chapter 6), the design occupant load, whether the sprinkler system is required where an automatic sprinkler system is provided, and any special stipulations. That list is a preview of the whole course. A temporary certificate can be issued before all work is done if the occupied portion is safe, and the official sets its time period (111.3). A certificate issued in error, on incorrect information, or in violation of the code can be suspended or revoked in writing (111.4).

Violations, stop work orders, and unsafe structures

Section 114 covers unlawful acts, notices of violation, prosecution, and penalties. Under Section 115 the official may issue a stop work order when work is contrary to the code or dangerous (115.1). It must be in writing, go to the owner, the owner's agent, or the person doing the work, state the reason, and state the conditions for resuming; the cited work stops immediately (115.2). In an emergency no written notice is needed first (115.3). Continuing after service, except work directed to remove the violation or unsafe condition, brings fines (115.4). Section 116.1 deems a structure unsafe for causes such as inadequate means of egress, inadequate light and ventilation, a fire hazard, illegal or improper occupancy, or inadequate maintenance. Related points: the official may enter to inspect at reasonable times after presenting credentials to an occupant and requesting entry, and if entry is refused, uses the remedies provided by law (104.6). Alternative materials and methods must be approved and must be at least equivalent in quality, strength, effectiveness, fire resistance, durability, and safety (104.11). Section 113 provides the means of appeals.

In the field

A nonprofit buys a vacant one-story retail building to turn into a small clinic and wants to "just paint and open." Before pricing anything, ask for the last certificate of occupancy. A shop becoming a clinic is a change of occupancy (Group M to Group B), which needs a permit and a new certificate under 105.1 and 111.1 even with only cosmetic work, and the existing-building code decides what upgrades follow. Then map the inspections: which will you request, and what must stay open until the inspector signs off? A contractor who closes a wall before the frame or penetration inspection has to open it again.

Practice questions

1. A community center wants a detached one-story storage shed under the base 2021 IBC exemption from permit in Section 105.2. What is the largest floor area that stays exempt?

  1. 120 square feet
  2. 200 square feet
  3. 150 square feet
  4. 250 square feet

2. A church plans a 6 ft wood privacy fence and, separately, an 8 ft masonry screen fence around a dumpster. Under Section 105.2, which fence is exempt from a permit?

  1. Both fences, since fences are never regulated
  2. Only the 8 ft fence, since masonry screen fences around dumpsters are exempt at any height
  3. Only the 6 ft fence, since 7 ft is the limit
  4. Neither fence, since every fence needs a permit

3. A retaining wall shows 3 ft 6 in. of exposed height above grade, and its footing bottom is 12 in. below grade. The wall retains only level soil. Under Section 105.2, is it exempt?

  1. Yes, because the visible height of 3 ft 6 in. is under the 4 ft limit measured from grade
  2. Yes, because retaining walls are never regulated
  3. No, because every retaining wall needs a permit regardless of height or what it retains
  4. No, because 4 ft is measured from the footing bottom, giving 4 ft 6 in.

4. A new concrete walkway is 18 in. above adjacent grade, is not over any basement or story below, and is part of an accessible route. Under Section 105.2, the walkway is:

  1. exempt, because it is under 30 in. above grade and not over a basement
  2. not exempt, because an accessible-route sidewalk is not covered
  3. exempt, because all sidewalks are exempt
  4. not exempt only if it is over 30 in. above grade, regardless of accessible route use

5. A design team submits an application for a Group B office building and does not respond to the plan review comments. Under Section 105.3.2, the application is deemed abandoned after how long, unless it is pursued in good faith?

  1. 30 days after filing
  2. 90 days after filing
  3. 180 days after filing
  4. One year after filing

6. A permit was issued and framing started, but work stopped for funding. Under Section 105.5, the permit becomes invalid if work stays suspended for:

  1. 30 days with no extension available
  2. 90 days, unless the contractor calls
  3. One year, with no extension available
  4. 180 days, unless a written extension is granted

7. Under Section 107.1 of the IBC, construction documents are prepared by a registered design professional:

  1. on every project, with no exceptions
  2. where required by the statutes of the jurisdiction
  3. only on projects over 10,000 square feet
  4. never, because the IBC does not address it

8. A four-story mass timber office building uses wood cover to provide connection fire-resistance ratings. Which 2021 inspection item applies?

  1. The Types IV-A, IV-B, and IV-C connection protection inspection, before other coverings
  2. The lowest floor elevation inspection in every case
  3. The energy efficiency inspection, and no other
  4. No added inspection, since mass timber follows the frame inspection under Section 110.3.4 only

9. An inspector arrives for a frame inspection on a Group M shell. The roof deck and framing are in, but fireblocking is unfinished and the rough plumbing has not been approved. Under Section 110.3.4, the inspector should:

  1. pass the frame now, since the roof deck and all framing are complete, and check fireblocking and rough plumbing later
  2. find the work not ready, because framing, fireblocking, and bracing must be in place and rough trades approved
  3. pass the frame, and check fireblocking at the final
  4. wait for the certificate of occupancy to inspect

10. Under Section 110.1, who has the duty to keep permitted work visible and accessible for inspection until it is approved?

  1. The owner or the owner's authorized agent
  2. The building official
  3. The design professional in responsible charge
  4. The neighboring property owner

11. A new Group R-2 building is in a flood hazard area. According to Section 110.3.12.1, what must be submitted before the final inspection?

  1. A copy of the recorded deed showing the boundaries of the flood zone
  2. The fire alarm shop drawings
  3. Lowest floor elevation documentation required by Section 1612.4
  4. A signed statement from the plumber that all fixtures are above base flood elevation

12. A dental practice will move into a former retail shop. The work is limited to painting and new carpet, but the use changes from Group M to Group B. Under Section 111.1, before the practice opens:

  1. no approval is needed, since the work is exempt finish work
  2. only a business license is needed
  3. the prior retail certificate covers the new use if the floor area is unchanged
  4. the building official must issue a certificate for the new use

13. A restaurant tenant space has a finished dining room, but the kitchen is still under construction. Under Section 111.3, the building official may:

  1. issue a permanent certificate for the whole building once the dining room is inspected and passed
  2. refuse any occupancy until every item in the whole building is done and signed off
  3. let the owner set the time period
  4. issue a temporary certificate of occupancy for the safe portion and set its time period

14. An official finds a serious hazard on a site during an emergency. Under Section 115.3, the official:

  1. must wait for a written notice to be served first
  2. is not required to give written notice before stopping the work
  3. may stop only work on the interior
  4. may stop work only after a court order

Glossary

Building official
The officer or agent charged with administering and enforcing the code, including issuing permits, making inspections, and issuing certificates of occupancy (Section 104).
Construction documents
The drawings, specifications, and related data submitted with a permit application (Section 107).
Certificate of occupancy
The document issued after final inspection that states the use, construction type, occupant load, and code edition, and allows the building to be used (Section 111).
Change of occupancy
A change in occupancy classification, or in the purpose or level of activity, where the code requires more safety than the current building provides (Chapter 2).
Stop work order
A written order to cease cited work, stating the reason and the conditions for resuming it (Section 115).
Special inspection
Inspection of specified work by a qualified inspector in addition to the building official's inspections, listed in the statement of special inspections (110.3.11).
Alternative method
A material, design, or method not prescribed by the code that the official approves as at least equivalent (104.11).