Lesson 7: Interior Finishes

IBC 803, 804, 806, 808 · 14 practice questions

0:00 / --:--

Reading

Chapter 8 of the 2021 IBC is about the surface of a building: the wall and ceiling finishes, floor finishes, and decorative materials people see every day. Fire runs fastest along a burning surface, so the code rates each finish for how quickly flame travels across it and how much smoke it makes, then limits which rating may go where. The rules matter in GCHS rehab and tenant-improvement work because paneling, carpet, and ceiling tile get swapped out constantly, and nobody stops to ask whether the new product meets Chapter 8.

Flame spread classes A, B, and C on a scale of 0 to 200 A horizontal scale of flame spread index from 0 to 200 drawn to scale. Class A covers 0 to 25, Class B covers 26 to 75, and Class C covers 76 to 200. A band below states that the smoke-developed index limit is 450 for all three classes. Three boxes below show the Table 803.13 class for a Group B building: exit stairs need A when not sprinklered and B when sprinklered, corridors need B and C, and rooms need C either way. Flame spread index, ASTM E84 (lower is safer) Drawn to scale: Class C covers most of the range Class A 0 to 25 Class B 26 to 75 Class C 76 to 200 0 25 75 200 Smoke-developed index: 450 or less for all three classes Table 803.13, Group B example (walls and ceilings) Exit stairs, passageways Not sprinklered: Class A Sprinklered: Class B Corridors Not sprinklered: Class B Sprinklered: Class C Rooms Not sprinklered: Class C Sprinklered: Class C
Flame spread is scored on one scale (shown to scale), then Table 803.13 says which class each part of the building needs.

The three classes (Section 803.1.2)

Wall and ceiling finishes are tested in a tunnel test, ASTM E84, which is also published as UL 723. It reports two numbers: a flame spread index and a smoke-developed index. For both, lower is better. Class A is a flame spread index of 0 to 25, Class B is 26 to 75, and Class C is 76 to 200. All three classes share one smoke limit: a smoke-developed index of 450 or less. A product whose flame spread is above 200, or whose smoke number is above 450, fits no class and cannot be used as an interior finish under these rules.

Key numbers
  • Class A: flame spread 0 to 25. Class B: 26 to 75. Class C: 76 to 200 (803.1.2)
  • Smoke-developed index: 450 or less for all three classes
  • Floor finish Class I: critical radiant flux 0.45 W/sq cm or more. Class II: 0.22 or more (804.2)
  • Fabric hangings and curtains: no more than 10 percent of the wall or ceiling they hang on (806.2)
  • Thin coverings under 0.036 in. applied directly to a wall or ceiling need not be tested (803.2)

The room corner test alternative

Section 803.1.1 allows a different route: the NFPA 286 room corner test, where a full-scale fire is built in the corner of a test room. A material that meets the acceptance criteria of 803.1.1.1, for example no flame spread to the ceiling during the 40 kW exposure, is treated as Class A. Section 803.13 also accepts NFPA 286 material anywhere the table asks for Class A.

What the chapter does not test

Three exemptions come up often. Under 803.2, a covering thinner than 0.036 inch applied directly to the wall or ceiling, such as paint or thin wallpaper, need not be tested. Under 803.3, exposed heavy timber (as defined by the code) is not subject to the finish limits, except in interior exit stairways, interior exit ramps, and exit passageways. Foam plastic used as a finish is not judged by Chapter 8 alone; Section 2603.9 controls it.

Table 803.13: which class goes where

Table 803.13 sets the required class by occupancy and by location. Three locations are listed, from most protected to least: interior exit stairways, ramps, and exit passageways; corridors and the enclosures of exit access stairs; and rooms and enclosed spaces. The exit path gets the strictest class because it must stay usable the longest. The table has one column group for buildings sprinklered throughout and one for buildings that are not. Here are the rows this course teaches, in our own layout (A is the best class, C the most permissive).

GroupSprinklered throughoutNot sprinklered
Exit stairs, passagewaysCorridorsRoomsExit stairs, passagewaysCorridorsRooms
A-1, A-2BBCAAB
A-3, A-4, A-5BBCAAC
B, E, M, R-1BCCABC
R-2CCCBBC
R-3CCCCCC
FCCCBCC
S-1, S-2CCCBBC

Some cells carry footnotes. For example, lobbies in Groups A-1, A-2, and A-3 must be at least Class B, Class C is allowed in assembly rooms with an occupant load of 300 or less in A-1 and A-2, and corridors in ambulatory care facilities need Class A or B. Always read the footnotes for your row.

How sprinklers change the answer

The sprinkler credit is already built into the table, so you never subtract a class yourself. You simply read the sprinklered column when the building is protected throughout by an NFPA 13 system (903.3.1.1) or an NFPA 13R system (903.3.1.2). Compare a Group B office building: in the exit stairs, the class drops from A to B, in corridors from B to C, and in offices it stays at C either way. Sprinklers lower the requirement in most cells, not all.

Floor finishes and coverings (Section 804)

Floors are tested differently, by a radiant panel test (ASTM E648 or NFPA 253) that reports critical radiant flux, and here a higher number is better, the opposite direction from the E84 index. Class I is 0.45 watts per square centimeter or more, and Class II is 0.22 or more. In every occupancy, floor coverings such as carpet must also pass the small-flame "pill test" (DOC FF-1, or ASTM D2859). In stair and ramp enclosures, exit passageways, corridors, and rooms that are not separated from corridors by full-height partitions, Section 804.4.2 requires at least Class I in Groups I-1, I-2, and I-3, and at least Class II in Groups A, B, E, H, I-4, M, R-1, R-2, and S. A building sprinklered throughout may drop one step: Class II where Class I is listed, and pill-test-only where Class II is listed. Groups R-3, F, and U are not listed, so only the pill test applies there.

Decorative materials, trim, and ceilings

Section 806.2 covers combustible curtains, draperies, and fabric hangings in Groups A, B, E, I, M, and in R-1, and in dormitories in Group R-2. They must pass a flame-resistance test (NFPA 701, or NFPA 289) and may not cover more than 10 percent of the wall or ceiling area they hang on. Exceptions allow up to 75 percent of wall area in a sprinklered Group A auditorium and up to 50 percent in sprinklered R-2 dormitory units; suspended fabric partitions in Groups B and M are not limited (they must still pass the flame test), and window coverings are outside the 10 percent limit. Combustible interior trim must be at least Class C and may not exceed 10 percent of the wall or ceiling area it is attached to (806.7, handrails and guards excluded). Floor-wall base 6 inches or less must be at least Class II (806.8). Acoustical ceilings must meet Section 803 and be installed to ASTM C635 and C636 (Section 808).

Worked example. A Group E classroom has a wall 10 feet high and 30 feet long, so the wall area is 10 x 30 = 300 square feet. Ten percent is 30 square feet. A fabric banner 4 feet by 6 feet is 24 square feet and fits. Adding a second banner 3 feet by 3 feet (9 square feet) brings the total to 33 square feet, which is over the limit for that wall. Now the finish class: the same school is not sprinklered, so the rooms (C), corridors (B), and exit stairs (A) come straight from the Group E row.

In the field

A small community center (Group A-3, not sprinklered) plans to replace corridor wainscot with wood paneling bought from a home center. The table calls for Class A in the corridors of a nonsprinklered A-3, and the paneling has no rating on the label. Before it goes up, ask for the manufacturer's test report showing the E84 flame spread and smoke numbers, or an NFPA 286 result. If the center later adds sprinklers throughout, the corridor requirement relaxes to Class B.

Practice questions

1. Under 2021 IBC Section 803.1.2, which flame spread index range defines a Class B interior wall and ceiling finish?

  1. 0 to 25
  2. 26 to 75
  3. 76 to 200
  4. 26 to 200

2. The smoke-developed index limit for interior wall and ceiling finish under Section 803.1.2 is:

  1. 450 or less for Class A, B, and C alike
  2. 25 for Class A, 75 for Class B, and 200 for Class C
  3. 200 or less for all three classes
  4. There is no smoke limit in the class definitions

3. A reviewer reads two ASTM E84 reports: ceiling tile 1 shows flame spread 20 and smoke 300, and tile 2 shows flame spread 60 and smoke 320. How are they classified?

  1. Both are Class A
  2. Tile 1 is Class B and tile 2 is Class C
  3. Both are Class C
  4. Tile 1 is Class A and tile 2 is Class B

4. A wall panel passes the NFPA 286 room corner test and meets the acceptance criteria of Section 803.1.1.1. For wall and ceiling finish, it is treated as:

  1. Class A
  2. Class B
  3. Class C
  4. Unclassified, so it must also be tested by ASTM E84

5. A painter applies a coating thinner than 0.036 inch directly to a gypsum board wall in a Group B office. Under Section 803.2, the coating:

  1. must be tested and be Class A
  2. need not be tested for flame spread and smoke
  3. must be tested and be at least Class C
  4. is limited to 10 percent of the wall area

6. An inspector reviewing a Group B office building that is not sprinklered checks the interior exit stairway. Under Table 803.13, the finish class required on the stairway walls is:

  1. Class A
  2. Class B
  3. Class C
  4. No class is required

7. A Group B office building is sprinklered throughout with an NFPA 13 system. An inspector finds Class C paneling in the corridors. Is this acceptable under Table 803.13?

  1. No, corridors always need Class A
  2. No, corridors need at least Class B
  3. Yes, but only if the system is NFPA 13R
  4. Yes, the sprinklered corridor column allows Class C

8. A church fellowship hall (Group A-3) is not sprinklered. Volunteers want new paneling in its corridors. Under Table 803.13, the minimum class for the corridor paneling is:

  1. Class B
  2. Class C
  3. Class A
  4. No minimum, because it is a small building

9. A Group R-2 apartment building is sprinklered throughout. What class does Table 803.13 require in its interior exit stairways?

  1. Class A
  2. Class B
  3. Class C
  4. None, because the stairs are enclosed

10. Under Section 804.2, a Class II floor finish has a critical radiant flux of:

  1. 0.45 watts per square centimeter or more
  2. Less than 0.22 watts per square centimeter
  3. 25 or less on the E84 scale
  4. 0.22 watts per square centimeter or more

11. A corridor in a nonsprinklered Group B building is being recarpeted. Under Section 804.4, what must the carpet satisfy?

  1. At least Class II critical radiant flux and the pill test
  2. Only the pill test
  3. At least Class I critical radiant flux and no pill test
  4. Nothing, because carpet is a decorative material

12. A Group E classroom has a wall 10 feet high and 25 feet long. What is the most wall area that combustible fabric hangings may cover under Section 806.2?

  1. 12.5 square feet
  2. 50 square feet
  3. 25 square feet
  4. 125 square feet

13. A sprinklered Group A auditorium is installed per 903.3.1.1. Under Section 806.2, combustible curtains and hangings may cover up to what share of the aggregate wall area?

  1. 10 percent
  2. 75 percent
  3. 25 percent
  4. 100 percent

14. Under Section 806.7, combustible interior trim (other than handrails and guards) must be at least Class C and may cover no more than what share of the wall or ceiling to which it is attached?

  1. 5 percent
  2. 10 percent
  3. 25 percent
  4. 50 percent

Glossary

Flame spread index
The number from the ASTM E84 tunnel test that shows how fast flame travels across a surface. Class A is 0 to 25, Class B is 26 to 75, and Class C is 76 to 200.
Smoke-developed index
The E84 number for how much smoke a material gives off. All three finish classes require 450 or less.
Interior finish
The exposed surface of walls, ceilings, and floors, plus decorative materials and trim, that Chapter 8 rates for fire performance.
Room corner test (NFPA 286)
A full-scale fire test in a test-room corner. A material meeting the 803.1.1.1 criteria is treated as Class A.
Critical radiant flux
The floor test result, in watts per square centimeter, at which flame stops spreading. Higher is better: Class I is 0.45 or more, Class II is 0.22 or more.
Pill test
A small-flame test (DOC FF-1 or ASTM D2859) that every floor covering, such as carpet, must pass in all occupancies.
Sprinklered throughout
Protected by an NFPA 13 system (903.3.1.1) or an NFPA 13R system (903.3.1.2); this is the condition for using the sprinklered columns of Table 803.13.