Lesson 13: Soils and Foundations

IBC 1803, 1804, 1806, 1808, 1809 · 14 practice questions

0:00 / --:--

Reading

Every load in a building, from the roof snow or rain to the people on the top floor, eventually ends up in the soil. Chapter 18 of the 2021 IBC is about that last handoff: how much the ground can carry, how it behaves when it gets wet or dry, and how deep and wide the footings have to be. In the Houston area the soil question is not academic. Much of the region sits on clay that swells in wet weather and shrinks in dry weather, and the cracked slabs, sticking doors and sloping floors in the older buildings GCHS inspects usually start there.

Footing section: depth below undisturbed ground and expansive clay notes A section through a stem wall and spread footing. The footing bottom is at least 12 inches below the undisturbed ground surface and at least 12 inches wide. Grade slopes away from the wall at 5 percent for 10 feet. A band of clay near the surface is marked as the zone of seasonal moisture change. Side notes give the four tests for expansive soil, the design options for expansive soil, and Houston-area context. Grade slopes away 5% for 10 ft (1804.4) Stem wall or foundation wall Slab or floor Zone of seasonal moisture change: clay swells, shrinks 12 in. min. below undisturbed ground (1809.4) 12 in. min. wide (1809.4) 6 in. thick under 1 floor (Table 1809.7) Bears on undisturbed soil (Table 1806.2) Expansive: ALL four (1803.5.3)Plasticity index 15 or moreOver 10% passes No. 200 sieveOver 10% finer than 5 micrometersExpansion index over 20Design options (1808.6)Design for movement (1808.6.1, .2)Or remove the soil (1808.6.3)Or stabilize, if approved (1808.6.4)Houston-area contextClay soils are common and moveRead the geotechnical reportKeep water away from the wall
A footing is measured from undisturbed ground, sized to the soil pressure, and protected from wet-and-dry swings by grading.

When a geotechnical investigation is required

Section 1803.2 says a geotechnical investigation is conducted under Sections 1803.3 through 1803.5 unless the building official waives it. The waiver is allowed only where satisfactory data from adjacent areas show that an investigation is not necessary for the conditions the section lists. That is a judgment call for the official, not a right of the builder, and a waiver is easy to defend on a small addition next to a building with a known soil history and hard to defend on a vacant lot. Under 1803.3 the soil is classified from borings, test pits or other exploration, and under 1803.4 a fully qualified representative of the registered design professional must be on site during all boring or sampling. Section 1803.5.2 adds a useful trigger: where soil classification, strength or compressibility is in doubt, or where someone claims a bearing value better than the code's own presumptive values, the official can require an investigation.

The report itself covers more than bearing capacity. Section 1803.5.4 asks whether the ground-water table is above or within 5 feet below the lowest floor where that floor is below the finished ground next to the foundation, unless waterproofing under Section 1805 is provided. Section 1803.5.5 lists what a deep foundation report must contain, such as recommended types and capacities, installation procedures and load tests.

What makes a soil expansive

Section 1803.5.3 gives a strict definition. A soil is considered expansive only if it meets all four of these:

  • a plasticity index of 15 or greater (ASTM D4318);
  • more than 10 percent of the particles pass the No. 200 sieve (ASTM D422);
  • more than 10 percent of the particles are smaller than 5 micrometers (ASTM D422); and
  • an expansion index greater than 20 (ASTM D4829).

The first three tests can be skipped if the expansion index test is performed, so in practice the geotechnical lab often runs the expansion index alone. The word "all" matters. A soil with a high plasticity index but a low expansion index is not expansive under this definition, and an inspector should read the report's classification rather than guess from the color or stickiness of the dirt.

Designing for expansive soil

Once a soil is expansive, Section 1808.6 gives the designer two ways to deal with it. Under 1808.6.1 the foundation is designed to resist the differential volume change and prevent uplift. Under 1808.6.2 a slab-on-ground, mat or raft foundation is designed using the Wire Reinforcement Institute and Concrete Reinforcing Steel Institute design method for slab-on-ground foundations or the Post-Tensioning Institute design standard PTI DC 10.5. Two exceptions let the designer skip that work: the expansive soil is removed to a depth that gives a constant moisture content and the replacement fill is not expansive (1808.6.3), or the building official approves stabilization of the soil (1808.6.4).

Key numbers
  • Expansive soil: plasticity index 15 or more, over 10 percent passing the No. 200 sieve, over 10 percent finer than 5 micrometers, and expansion index over 20, all four (1803.5.3)
  • Ground-water check: table above or within 5 ft below the lowest floor that is below adjacent grade (1803.5.4)
  • Minimum footing depth: 12 in. below the undisturbed ground surface; minimum width 12 in. (1809.4)
  • Grading: slope of at least 5 percent (1:20) away from the wall for at least 10 ft (1804.4)
  • Presumptive vertical bearing: 1,500 psf for clay up to 12,000 psf for crystalline bedrock (Table 1806.2)

Presumptive load-bearing values

Section 1806.2 caps the load-bearing values used in design for soils near the surface at the values in Table 1806.2, unless data to substantiate higher values are submitted and approved. The table sorts soil and rock into five classes. The layout below is rebuilt with only what this lesson teaches.

ClassMaterialVertical bearing (psf)Lateral bearing (psf per ft of depth)
1Crystalline bedrock12,0001,200
2Sedimentary and foliated rock4,000400
3Sandy gravel and gravel (GW, GP)3,000200
4Sand, silty sand, clayey sand, silty gravel, clayey gravel (SW, SP, SM, SC, GM, GC)2,000150
5Clay, sandy clay, silty clay, clayey silt, silt, sandy silt (CL, ML, MH, CH)1,500100

Two footnote-style rules matter in the field. Lateral bearing may be increased by the tabular value for each additional foot of depth, up to 15 times the tabular value (1806.3.3), and for class 5 soils the lateral sliding resistance cannot exceed one-half of the dead load (1806.3.2). Notice where the everyday Gulf Coast soils land: the clays are class 5, the lowest bearing value in the table, and they are also the soils most likely to be expansive. A soil can be weak and moving at the same time.

A worked example. A column on a small community building carries 60,000 pounds and bears on class 5 clay at the presumptive 1,500 psf. The footing area needed is 60,000 divided by 1,500, which is 40 square feet. A square footing needs a side of the square root of 40, about 6.32 feet, so a 6 foot 4 inch square footing (about 40.1 square feet) is the smallest whole-inch size that works. The same column on class 4 sand at 2,000 psf needs only 30 square feet, roughly a 5 foot 6 inch square.

Footing depth, width and frost

Section 1809.4 sets the floor for every footing: the bottom is at least 12 inches below the undisturbed ground surface, and the width is at least 12 inches. "Undisturbed" is the key word. Fill placed last week does not count as ground, so the depth is measured from the natural surface (or the cut surface), not from a graded pad. Section 1809.5 adds frost protection where it applies. Footings extend below the frost line of the locality, or are built to ASCE 32, or bear on solid rock. There is an exception for free-standing Risk Category I buildings of 600 square feet or less if light-frame (400 square feet if not light-frame) with an eave height of 10 feet or less. Section 1809.5.1 also protects exterior landings of required exits that have outward-swinging doors, to the extent needed to keep the doors operable. Frost depth is a local number and it is shallow on the Gulf Coast, so in Houston the 12-inch minimum and the soil report usually govern; check the adopted code and local amendments for the value your jurisdiction uses.

Prescriptive footings for light-frame walls

Where a specific design is not provided, Table 1809.7 gives footing sizes under light-frame walls by the number of floors supported. One floor calls for a 12 inch wide, 6 inch thick footing. Two floors call for 15 inches wide and 6 inches thick, and three floors call for 18 inches wide and 8 inches thick. A footing may carry a roof in addition to the floors listed, and interior stud-bearing walls may use isolated footings twice the table width spaced not more than 6 feet on center. Under walls other than light-frame, Section 1809.8 requires plain concrete footings to be at least 8 inches thick at the edge (with a 6 inch allowance for Group R-3 within limits). A prescriptive table does not override an engineered design or an expansive-soil report; if the plans include a design, build the design.

Grading and drainage at the foundation

Water is what moves clay, so the code controls it at the surface. Section 1804.4 requires the ground next to the foundation to slope away at a rate of at least 5 percent (1:20) for at least 10 feet measured perpendicular to the wall. If a lot line or obstruction prevents 10 feet, the 5 percent slope runs to an approved alternative means of diverting water. Swales within 10 feet slope at least 2 percent, and impervious surfaces within 10 feet slope at least 2 percent away from the building. Where climate or soil conditions warrant, the slope may be reduced to 1:48 (2 percent).

In the field

On a rehab of a one-story community hall built on a slab, GCHS found a long diagonal crack at the corner, doors that stuck in August, and a downspout that discharged at the foundation. The bare dirt against the wall sloped toward the building, and a hose bib leaked into the planting bed. Moisture at the edge of a slab on clay makes that edge heave while the dry center stays put. Before quoting any slab repair, look first at grading, downspouts, leaks and trees, ask for the original geotechnical report, and check that the fix drains water 10 feet away from the wall. Otherwise the crack comes back.

Deep foundations and where to look next

When shallow footings cannot carry the load, or the soil near the surface is too weak or too moving, the designer uses deep foundations such as driven piles or drilled piers, covered in Section 1810. Section 1810.1.1 requires a geotechnical investigation under Section 1803 for them, and the inspection of deep foundations is a special inspection item you will meet in Lesson 16. For the rest of the chapter, use this map: 1805 dampproofing and waterproofing, 1806 presumptive values and lateral resistance, 1807 foundation walls, retaining walls and embedded posts, 1808 foundations in general, and 1809 shallow foundations.

Practice questions

1. Under 2021 IBC Section 1803.5.3, a soil is considered expansive only when it meets:

  1. Any one of the four criteria, since each test alone shows that the soil will swell
  2. A plasticity index of 15 or more, whatever the sieve, clay-size, and expansion index results show
  3. All four: PI of 15 or more, the sieve and clay-size fractions, and an expansion index over 20
  4. A classification as clay under the soil classification standard, whatever the individual test results may show

2. A geotechnical lab tells a designer that the first three tests under 1803.5.3 need not be run when the expansion index test is performed. Which statement is correct?

  1. That is correct: tests for the first three items are not required if the expansion index test is run
  2. That is wrong: all four tests must always be run, and the expansion index test never replaces the other three
  3. That is correct, but only for Group R occupancies and only with the building official's approval
  4. That is wrong: the plasticity index test can never be skipped, even when the expansion index is run

3. A slab-on-ground for a Group B office is on expansive soil and is designed under Section 1808.6.2. The design method that section names is:

  1. The prescriptive footing sizes in Table 1809.7 for light-frame construction
  2. The presumptive bearing values in Table 1806.2 with a reduced allowable pressure
  3. The empirical masonry design provisions of Chapter 21 for slabs and mats
  4. The WRI/CRSI slab-on-ground design method or PTI DC 10.5

4. An inspector reads the plans for a Group S-1 warehouse on expansive clay. The designer avoids designing for soil movement by taking the exception in Section 1808.6.3. What must the plans show?

  1. A 6 in. gravel layer and a vapor retarder under the slab, after which the soil is treated as non-expansive by the code
  2. Removal of the expansive soil to a depth of constant moisture content, replaced with non-expansive fill
  3. Footings widened to 24 in. under every wall and deepened to 30 in. below grade
  4. The class 4 sand presumptive bearing value used in place of the clay value, with no other change

5. Under Table 1806.2, the presumptive vertical foundation pressure for class 5 soil (clay, sandy clay, silty clay, clayey silt, silt, sandy silt) is:

  1. 2,000 psf
  2. 1,500 psf
  3. 3,000 psf
  4. 4,000 psf

6. A column carries 90,000 lb and bears on class 4 sand (SW, SP, SM, SC, GM, GC) at the presumptive vertical value. The minimum footing bearing area is:

  1. 60 square feet
  2. 30 square feet
  3. 22.5 square feet
  4. 45 square feet

7. An inspector checking a Group R-2 plan sees a continuous footing that carries 4,500 lb per linear foot on class 5 clay at the presumptive value. The minimum footing width needed for bearing is:

  1. 3 ft 0 in.
  2. 1 ft 6 in.
  3. 2 ft 3 in.
  4. 1 ft 0 in., the code minimum width

8. Under Section 1806.3.3, lateral bearing may be increased for each additional foot of depth by the tabular value, up to a maximum of:

  1. 2 times the tabular value
  2. 5 times the tabular value
  3. 15 times the tabular value
  4. 30 times the tabular value

9. For class 5 soils, Section 1806.3.2 limits lateral sliding resistance to no more than:

  1. The full dead load
  2. One-quarter of the dead load
  3. Twice the dead load
  4. One-half of the dead load

10. An inspector measures a footing bottom at 10 in. below the undisturbed ground surface on a Houston-area site where frost is not a factor. Under Section 1809.4, this footing:

  1. Complies; the minimum depth is 6 in. below the undisturbed ground surface
  2. Complies; the minimum depth is 8 in. below the undisturbed ground surface
  3. Is too shallow; the minimum is 12 in. below undisturbed ground
  4. Complies if the footing is at least 15 in. wide and set on undisturbed soil

11. Which building may be exempt from frost protection of footings under Section 1809.5?

  1. A free-standing light-frame Risk Category I building of 600 sq ft or less, eave height 10 ft or less
  2. Any one-story Group B building of 600 sq ft or less with an eave height of 10 ft or less
  3. A free-standing light-frame Risk Category II building of 1,000 sq ft or less with an eave height of 10 ft
  4. Any Group S-2 building with an eave height over 10 ft that is free-standing and light-frame

12. A light-frame wall on a small multifamily building supports two floors, and no specific footing design is provided. Table 1809.7 calls for a footing of at least:

  1. 12 in. wide and 6 in. thick
  2. 15 in. wide and 6 in. thick
  3. 18 in. wide and 8 in. thick
  4. 15 in. wide and 8 in. thick

13. An inspector measures 2 in. of fall in 10 ft away from the wall of a Group A-3 community building. Under Section 1804.4, this grading is:

  1. Compliant, because a 1:20 slope means 2 in. of fall in 10 ft of horizontal distance
  2. Compliant, because any fall away from the wall is acceptable for a community building
  3. Compliant only if the surface is an impervious slab, which needs just 1 percent
  4. Not compliant; it is below even the 2 percent (1:48) allowed for soil conditions

14. Section 1803.5.4 requires a geotechnical report to address the ground-water table when:

  1. The water table is at or within 5 ft below a below-grade lowest floor, unless Section 1805 waterproofing is used
  2. Any building is built within a floodplain, whether or not it has a below-grade floor, unless deep foundations are used
  3. The table is more than 20 ft below the lowest floor of the building, unless Section 1805 waterproofing is provided
  4. Only when deep foundations are used and the table is within 10 ft of the footing bottoms, in any occupancy

Glossary

Undisturbed ground
The natural or cut soil surface, not recent fill; footing depth under 1809.4 is measured from it.
Expansive soil
Soil that meets all four tests in 1803.5.3 (plasticity index, two particle-size tests, and expansion index) and swells and shrinks with moisture.
Plasticity index
A lab measure of how much a soil's moisture can change while it stays plastic; 15 or more is one of the four expansive-soil criteria.
Presumptive load-bearing value
A conservative soil pressure listed in Table 1806.2; design values for near-surface soils may not exceed it unless data supporting a higher value are approved.
Lateral bearing
The resistance of soil to sideways push on a foundation, given in psf per foot of depth in Table 1806.2.
Frost line
The depth to which ground freezes in a locality; footings must extend below it where frost protection applies.
Stem wall
The short foundation wall that rises from a footing to support the floor or wall above.
Geotechnical investigation
Borings, test pits and lab tests that classify the soil and give its strength and behavior, done under Section 1803.