Lesson 8: Wiring Methods and Conductor Ampacity

NEC 300.4, 300.5, 300.11, 310.15, Tables 300.5(A) and 310.16 · 14 practice questions

0:00 / --:--

Reading

Two questions decide most wiring-method problems in commercial work: is the wiring protected where it goes, and is the conductor big enough once the heat and the crowding are counted. Article 300 answers the first, and Article 310 answers the second. This lesson covers protection in framing and fire-rated assemblies, the burial depths in Table 300.5(A), and how to use Table 310.16 with the ambient temperature and adjustment factors from the 2023 NEC. Local adoption governs which edition is enforced (Lesson 1).

Minimum cover for four buried wiring methods under Table 300.5(A) A cross section of earth shows four buried installations measured from finished grade to the top of the wiring. Direct burial cable in Column 1 needs 24 inches of cover. Listed PVC or EMT in Column 3 needs 18 inches. Rigid or intermediate metal conduit in Column 2 needs 6 inches. Any of these methods under a street, driveway or parking lot needs 24 inches, measured from the top of the paving. Minimum cover, Table 300.5(A), 0 to 1000 V ac (measured to the top of the wiring) Finished grade 24 in. 18 in. 6 in. 24 in. Paving Direct burial cable Column 1, all locations UF, USE, or MC for burial Listed PVC or EMT Column 3, all locations No concrete around it RMC or IMC Column 2, all locations Steel needs the least cover Under paving Streets, driveways, lots 24 in. in every column Under a building: 0 in. of cover, but the wiring must be in a raceway (300.5(C)). Rock in the way: metal or listed nonmetallic raceway under 2 in. of concrete down to rock (Note 5).
Cover is the shortest distance from the top of the buried wiring to the finished grade, concrete or similar cover. A steel conduit needs only 6 in. in open ground, while direct burial cable needs 24 in., and paving raises every method to 24 in.

Protecting wiring in framing

Where a cable or raceway passes through bored holes in wood joists, rafters or studs, the edge of the hole must be at least 1-1/4 in. from the edge of the member. If that cannot be done, a steel plate or bushing at least 1/16 in. thick must cover the wiring, and no plate is needed for RMC, IMC, PVC, RTRC or EMT (300.4(A)(1)). Wiring run parallel to framing or furring follows the same 1-1/4 in. distance where nails or screws are likely to hit it, with the same 1/16 in. plate or sleeve as the fix (300.4(D)). In commercial work this comes up most in wood-framed Type V buildings, and around wood blocking and nailers in any building.

Support, fire-rated assemblies and firestopping

Wiring above a suspended ceiling cannot be supported by the ceiling grid, and support wires that are not secure cannot be the only support (300.11(B)). In a fire-rated floor-ceiling or roof-ceiling assembly, wiring may not be secured to or supported by the ceiling assembly or its support wires, and an independent means of support is required (300.11(B)(1)). Openings around electrical penetrations of fire-resistance-rated walls, floors and ceilings are firestopped with approved methods so the rating is kept (300.21). The listed assembly tells you the method, and the building code sets the rating.

Burial depths

Direct-buried cable, conduit and other raceways meet the cover in Table 300.5(A), measured from the top of the wiring to the top of finished grade, concrete or similar cover (Note 1). The columns are: 1, direct burial cable; 2, RMC or IMC; 3, EMT, listed direct burial nonmetallic raceway with no concrete, and other approved raceways; 4, residential branch circuits of 120 V or less with GFCI and 20 A protection at most; 5, irrigation and landscape lighting of 30 V or less. Columns 1 to 3 cover most commercial work.

LocationCol 1 cableCol 2 RMC, IMCCol 3 EMT, PVC
All locations not listed below24 in.6 in.18 in.
In trench below 2 in. of concrete18 in.6 in.12 in.
Under 4 in. exterior slab, no vehicles, slab 6 in. beyond18 in.4 in.4 in.
Under streets, roads, alleys, driveways, parking lots24 in.24 in.24 in.
Airport runways and adjacent areas18 in.18 in.18 in.

Other rules ride with the table. Where a Column 1 to 3 method is used for a Column 4 or 5 circuit, the shallowest depth applies (Note 4). Underground cable under a building goes in a raceway (300.5(C)). Cables that emerge from grade are protected by an enclosure or raceway from the required cover depth, never more than 18 in. down, up to 8 ft above grade (300.5(D)(1)). Underground service conductors not encased in concrete and buried 18 in. or more get a warning ribbon 12 in. above them (300.5(D)(3)). The inside of an underground raceway is a wet location, so the conductors must be a wet-location type (300.5(B)). Where rock stops you, the wiring goes in metal or listed nonmetallic raceway under 2 in. of concrete down to rock (Note 5).

Table 310.16 and its four conditions

Table 310.16 gives ampacities for conductors rated 0 to 2,000 V, in raceway, cable or earth, when all four things are true: the conductor is rated 60, 75 or 90 degrees C, the ambient is 30 degrees C (86 degrees F), there are not more than three current-carrying conductors, and the rest of the rules are met. Change any condition and the table value must be corrected. Here are the copper rows most used.

Copper size60 C75 C90 C
12 AWG20 A25 A30 A
10 AWG30 A35 A40 A
8 AWG40 A50 A55 A
6 AWG55 A65 A75 A
4 AWG70 A85 A95 A
1/0125 A150 A170 A
4/0195 A230 A260 A

Correction for ambient temperature

Where the ambient is not 30 degrees C, multiply the ampacity by the factor in Table 310.15(B)(1)(1) for the conductor's temperature rating (310.15(B)(1)). A Houston attic or mechanical room in summer commonly lands in the 41 to 45 degree C band (105 to 113 degrees F).

Ambient60 C75 C90 C
31 to 35 C (87 to 95 F)0.910.940.96
36 to 40 C (96 to 104 F)0.820.880.91
41 to 45 C (105 to 113 F)0.710.820.87
46 to 50 C (114 to 122 F)0.580.750.82

Raceways or cables in direct sun on a roof, where the bottom of the wiring is less than 3/4 in. above the roof, add 33 degrees C (60 degrees F) to the outdoor temperature before choosing the factor (310.15(B)(2)). XHHW-2 conductors are not subject to that adder.

Adjustment for more than three conductors

When more than three current-carrying conductors share a raceway or cable, each conductor's ampacity is reduced by the Table 310.15(C)(1) percentage, and paralleled conductors each count (310.15(C)(1)).

Current-carrying conductorsPercent of ampacity
4 to 680
7 to 970
10 to 2050
21 to 3045
31 to 4040
41 and above35

What counts matters. The count includes spare conductors, but not conductors tied to loads that cannot run at the same time (Table note). A grounding or bonding conductor is not counted (310.15(F)). A neutral that carries only the unbalanced current is not counted, but the neutral of a 3-wire circuit taken from a 4-wire wye system is counted, and so is the neutral on a 4-wire wye circuit that serves mostly nonlinear loads such as LED drivers and computers (310.15(E)). Raceways 24 in. or shorter are exempt from adjustment (310.15(C)(1)(b)).

Putting it together: corrections, adjustments and terminals

Correction and adjustment can be applied to the ampacity of the conductor's own temperature rating, such as the 90 degree C column for THHN, as long as the result does not exceed the ampacity at the termination's temperature rating (310.15(A), 110.14(C)). Terminals for circuits of 100 A or less, or marked for 14 to 1 AWG, are treated as 60 degrees C unless the equipment is listed and marked otherwise. Terminals for larger circuits are treated as 75 degrees C (110.14(C)(1)). So the answer is the smaller of two checks: the derated value, and the table value at the termination temperature.

Worked example: two circuits in one attic conduit

Two 208 V three-phase, 3-wire circuits feed shop equipment at 45 A each, noncontinuous, on 50 A breakers. They run in one EMT through an attic with a design temperature of 110 degrees F, using THHN copper.

  1. Count: three conductors plus three is six current-carrying conductors. The grounding conductor is not counted. Table 310.15(C)(1) gives 80 percent.
  2. Ambient: 110 degrees F is in the 105 to 113 degrees F row, so the 90 degree C factor is 0.87.
  3. Try 8 AWG: 55 A x 0.87 x 0.80 = 38.3 A. That is less than 45 A, so 8 AWG fails.
  4. Try 6 AWG: 75 A x 0.87 x 0.80 = 52.2 A. That is at least 50 A, so it passes.
  5. Termination check: the circuit is 100 A or less, so terminals are 60 degrees C, where 6 AWG is 55 A. The derated 52.2 A does not exceed 55 A.

The answer is 6 AWG THHN on 50 A breakers. If the loads were nonlinear and each circuit carried a counted neutral, there would be eight conductors and 70 percent, so 6 AWG would drop to 75 x 0.87 x 0.70 = 45.7 A, which still covers 45 A but barely.

Key numbers
  • Cover, all locations: cable 24 in., RMC or IMC 6 in., EMT or listed PVC 18 in. (Table 300.5(A))
  • Under streets, driveways and parking lots: 24 in. for every column
  • Bored wood members: hole edge 1-1/4 in. from the edge, else 1/16 in. steel plate (300.4(A)(1))
  • Table 310.16 assumes 30 degrees C and no more than three current-carrying conductors
  • Adjustment: 4 to 6 conductors 80 percent, 7 to 9 70, 10 to 20 50 (Table 310.15(C)(1))
  • Ambient 41 to 45 degrees C: 0.87 at 90 C, 0.82 at 75 C, 0.71 at 60 C (Table 310.15(B)(1)(1))
  • Rooftop adder of 33 degrees C only if the raceway is under 3/4 in. above the roof (310.15(B)(2))
  • The corrected and adjusted ampacity may not exceed the termination's ampacity (110.14(C))

In the field

A GCHS rehab of a small clinic runs a new feeder for rooftop units. The plan review checks two things. First, that the underground stub-up from the parking lot uses the right cover, 24 in. under the paving and a steel elbow where it rises. Second, that the conduit fill sheet counts every current-carrying conductor and lists the roof ambient and the height of the conduit above the roof. In the field, look for EMT sitting right on the roof and for neutrals that were left out of the count on LED and computer circuits.

Practice questions

1. A Group M shopping center runs 480 V direct burial UF cable to a parking lot light pole under the paved lot. What minimum cover does Table 300.5(A) require for the cable under the paving?

  1. 18 in., the depth for one- and two-family dwelling driveways in Column 1
  2. 12 in., the depth for Column 3 wiring in a trench below 2 in. of concrete
  3. 24 in., measured from the top of the pavement to the top of the cable
  4. 6 in., the depth for landscape lighting cable under a slab with vehicles

2. Rigid metal conduit carrying 208Y/120 V feeders is buried in an open landscaped area beside a Group A-3 community center. What minimum cover does Table 300.5(A) require, Column 2, all locations?

  1. 6 in.
  2. 12 in., the same as direct burial cable in a trench below concrete
  3. 18 in., the same as listed PVC conduit
  4. 24 in., the same as direct burial cable

3. A Group B office needs a feeder in Schedule 40 PVC conduit listed for direct burial, with no concrete around it, run under an open lawn. What minimum cover does Table 300.5(A) give for this nonmetallic raceway?

  1. 6 in., because the conduit is protected by its jacket
  2. 12 in., because the conduit is under grass
  3. 24 in., because all nonmetallic wiring needs direct burial cable depth
  4. 18 in.

4. PVC conduit for a Group B building lies under a 4 in. thick exterior concrete slab that carries no vehicles and extends at least 6 in. beyond the conduit on each side. What minimum cover applies to the PVC in Column 3?

  1. 12 in., the trench-below-concrete depth
  2. 4 in., the Column 3 depth under a qualifying slab
  3. 18 in., the all-locations depth
  4. 24 in., the depth under parking lots

5. A trench crosses beneath the footprint of a new Group R-2 apartment building at a slab that will be poured later. What does 300.5(C) require of underground conductors under the building?

  1. They must be installed in a raceway, with cover of 0 in. in the table
  2. They may be direct burial cable at 6 in. of cover under the slab if the cable is UF
  3. They must be in a raceway buried at least 18 in. below the slab
  4. They may be direct burial cable if buried at least 24 in. deep

6. Direct burial cable buried at 24 in. rises to a wall-mounted disconnect on a Group B building. How far must the protection extend, under 300.5(D)(1)?

  1. From 24 in. below grade up to 8 ft above grade
  2. From 6 in. below grade up to 6 ft above grade
  3. From 18 in. below grade up to 8 ft above grade
  4. From grade level up to 18 in. above grade

7. An underground 400 A service lateral in PVC serves a Group B strip center. It is buried 24 in. and is not encased in concrete. What does 300.5(D)(3) require?

  1. A warning ribbon placed directly on top of the conduit before backfill
  2. A warning ribbon in the trench at least 12 in. above the installation
  3. A concrete cap of at least 2 in. over the conduit, in place of the ribbon
  4. A ribbon 6 ft above the installation at the surface

8. An electrician runs MC cable through a hole in a wood stud where the hole edge is 3/4 in. from the stud edge in a Group R-2 building. What does 300.4(A)(1) require?

  1. Nothing, because the armor of MC cable already protects it from nails and screws
  2. A plastic sleeve at least 1/8 in. thick
  3. A steel plate only if the hole exceeds 1-1/4 in. in diameter
  4. A steel plate or bushing at least 1/16 in. thick covering the cable

9. In a Group B tenant space, an electrician clamps an EMT run to the ceiling support wires of a rated floor-ceiling assembly. What does 300.11(B)(1) say?

  1. Allowed, if the EMT is secured within 3 ft of every box and every 10 ft
  2. Allowed, if the support wires are at least 12 gauge and secured at both ends
  3. Not allowed, because independent support is required in a rated cavity
  4. Not allowed only if the ceiling assembly is rated more than 2 hours

10. A 12 AWG THHN copper conductor in EMT (three current-carrying conductors) runs through a Group B attic at 43 degrees C. All terminations are rated 60 degrees C. What is the highest ampacity that may be used?

  1. 20 A, the limit set by the 60 C terminals
  2. 26.1 A, the 90 C value of 30 A times 0.87
  3. 20.5 A, the 75 C value of 25 A times 0.82
  4. 30 A, the uncorrected 90 C value from Table 310.16

11. Nine current-carrying 12 AWG THHN copper conductors share one EMT in a Group B office at 30 degrees C. Using the 90 degree C column, what is the adjusted ampacity of each conductor under Table 310.15(C)(1)?

  1. 24 A, from 30 A x 0.80
  2. 15 A, from 30 A x 0.50
  3. 30 A, since the ambient is 30 degrees C
  4. 21 A, from 30 A x 0.70

12. Three 4-wire, 208Y/120 V circuits, each with three phase conductors and a neutral, run in one EMT to a Group B office where most of the load is LED drivers and computers. How many conductors are counted, and what percentage applies?

  1. 9 conductors, because neutrals are never counted, so 70 percent
  2. 12 conductors, neutrals count with nonlinear loads: 50 percent
  3. 10 conductors, counting the neutrals of two circuits, so 50 percent
  4. 12 conductors, because every conductor counts, so 45 percent

13. A 3-phase, 3-wire feeder in a Group B building has three phase conductors, one grounding conductor and, as the drawings show, two spare conductors in the same raceway. How many conductors are counted for Table 310.15(C)(1)?

  1. 6, because every conductor in the raceway counts, so 80 percent
  2. 3, because only conductors that are energized count, so no adjustment applies
  3. 5, since spares count and the grounding conductor does not: 80 percent
  4. 8, because the spares count double, so 70 percent

14. EMT runs across the roof of a Group B building, held 2 in. above the roof surface and in direct sun. Under 310.15(B)(2), what temperature adder is applied to the outdoor temperature?

  1. None, since the adder applies only where the raceway bottom is under 3/4 in. above the roof
  2. 33 degrees C, because any conduit on a roof is exposed to direct sun and reflected heat
  3. 20 degrees C, because raceways more than 1 in. above the roof get a smaller adder
  4. 33 degrees C, but only for conductors other than THHN or THWN-2 insulation

Glossary

Ampacity
The current a conductor can carry continuously without exceeding its temperature rating, under the conditions of use.
Cover
The shortest distance from the top of buried wiring to the top of finished grade, concrete or similar cover.
Direct burial
A wiring method installed in earth with no raceway, using cable listed and marked for it.
Ambient temperature
The temperature of the air or earth around the wiring; Table 310.16 assumes 30 degrees C (86 degrees F).
Correction factor
A multiplier for ambient temperature taken from Table 310.15(B)(1)(1), applied to the table ampacity.
Adjustment factor
A percentage from Table 310.15(C)(1) that reduces ampacity when more than three current-carrying conductors are bundled.
Current-carrying conductor
A conductor that carries load current and counts toward adjustment; grounding conductors do not count, and neutrals count in some cases.
Termination temperature rating
The maximum conductor temperature the equipment terminals are rated for, usually 60 or 75 degrees C, which caps the final ampacity.
Firestopping
An approved seal around a penetration that keeps a fire-resistance-rated wall, floor or ceiling rated.