Lesson 5: Commercial Kitchen Hoods and Grease Ducts

IMC 506, 507, 508, 509 · 14 practice questions

0:00 / --:--

Reading

A commercial kitchen exhaust system is a fire safety system dressed up as ventilation. Grease from the cooking line coats every surface it touches, and a grease fire inside a duct can travel through a building faster than almost any other mechanical failure. Sections 506 through 509 of the 2021 IMC therefore treat the hood, duct, fan, makeup air and fire suppression as one assembly, and the figure below follows it from the cooking surface up to the roof. Local adoption governs, and the fire official may review kitchen exhaust as well.

Type I hood and grease duct in section with clearances and slope A section through a restaurant kitchen. A Type I canopy hood sits over a cooking appliance with a 6 inch minimum overhang and a lip no more than 4 feet above the cooking surface. The grease duct rises through the ceiling into a dashed rated enclosure, runs horizontally with a slope of one quarter inch per foot toward the hood, and rises through the roof to an upblast fan whose discharge is 40 inches above the roof. Below the drawing three columns list hood, grease duct and outlet requirements. Type I hood and grease duct in section (schematic, not to scale) Roof Ceiling Appliance Type I hood Fan Rated enclosure (1 hr min.) Slope 1/4 in. per ft (2%) toward the hood; 1 in. per ft where a horizontal run exceeds 75 ft 4 ft max. 6 in. min. Filters, 45 degrees min. 40 in. min. 18 in. min. Hood (507) Steel 18 gage or stainless 20 MSG 18 in. min. to combustibles Overhang 6 in. min. on open sides Lip 4 ft max. above cooking surface Fire suppression required (509.1) Grease duct (506.3) Steel 16 gage or stainless 18 gage External liquid-tight welds Velocity 500 fpm or more 18 in. combustible; 3 in. noncomb. No fire or smoke dampers in duct Outlet and air (506, 508) 10 ft from buildings, lot lines 10 ft above adjoining grade 10 ft from, or 3 ft above, intakes Makeup air about equal to exhaust Small squares on duct: cleanouts
Read the system from the cooking surface up: hood, riser, sloped run inside a rated enclosure, fan, and outlet above the roof.

Type I or Type II (507.2 and 507.3)

A Type I hood is required over cooking appliances that produce grease or smoke, and the code names medium-duty, heavy-duty and extra-heavy-duty appliances (507.2). Chapter 2 sorts the equipment. Light duty covers ovens, kettles and steamers. Medium duty covers griddles, fryers and electric ranges. Heavy duty covers under-fired broilers, gas open-burner ranges, woks and smokers. Extra-heavy duty means open-flame combustion of solid fuel. A Type II hood goes over dishwashers and other heat- or moisture-producing appliances that make no grease or smoke, and over appliances that produce combustion products but no grease (507.3). Where cooking appliances do not require a Type II hood, the space is exhausted at 0.70 cfm per square foot, counting each such appliance as at least 100 square feet.

If any appliance under one hood needs Type I, the whole hood is Type I, and then the entire system (hood, duct, fan and makeup air) follows Sections 506 through 509 (507.1). An extra-heavy-duty hood cannot cover other duty classes and needs its own exhaust system (507.2.2).

Hood construction, filters and size (507.2 and 507.4)

A Type I hood is steel of at least No. 18 gage or stainless steel of at least No. 20 MSG, supported by noncombustible members, with external joints and seams welded or brazed liquid tight (507.2.3 to 507.2.5). It keeps 18 inches from combustible construction. A hood listed for less follows its listing, and gypsum board on noncombustible structure needs no clearance if a smooth noncombustible surface covers the wall 18 inches around the hood (507.2.6).

Grease filters are listed, readily removable and set at least 45 degrees from horizontal over a drip tray (507.2.8). Their lowest edge sits at least 6 inches above a cooking surface without exposed flame, 24 inches over exposed flame and burners, and 42 inches over charcoal and charbroil appliances (Table 507.2.8). A canopy hood overhangs the appliance by at least 6 inches on every open side, with its front lip no more than 4 feet above the cooking surface (507.4.1). A non-canopy hood is no more than 3 feet above the surface and set back no more than 1 foot (507.4.2). Each exhaust outlet in a hood serves no more than 12 feet of hood (507.1.5).

How much air (507.5)

The exhaust rate depends on the hood type and on the heaviest-duty appliance under it; mixing lighter appliances under the same hood does not lower the rate. The code gives cubic feet per minute per linear foot of hood; the table shows two common types. An island canopy needs more air because no wall helps contain the plume, and an eyebrow hood is not allowed over heavy or extra-heavy appliances. A Type II hood over a dishwasher is 100 cfm per linear foot (507.5.5).

Duty of the heaviest applianceWall-mounted canopy (cfm per ft)Single island canopy (cfm per ft)
Light200400
Medium300500
Heavy400600
Extra-heavy550700

Worked example. A 10-foot wall-mounted canopy covers a medium-duty fryer and a heavy-duty gas open-burner range. The heavy-duty appliance governs, so the net exhaust is 400 x 10 = 4,000 cfm. Makeup air must be about 4,000 cfm too, and one outlet is enough because an outlet may serve 12 feet of hood. As a single island canopy the same hood would need 600 x 10 = 6,000 cfm. Slope has arithmetic too: a 40-foot horizontal run at 1/4 inch per foot rises 10 inches from the hood end, while an 80-foot run needs 1 inch per foot and rises 80 inches, which is why long runs are a design problem to catch early.

Grease duct construction (506.3)

Grease ducts are steel of at least No. 16 gage or stainless steel of at least No. 18 gage (506.3.1.1). Joints, seams and penetrations receive a continuous liquid-tight weld or braze on the external surface, (506.3.2). Screws, bolts and rivets must not penetrate the duct wall, and supports are noncombustible (506.3.3). Before any part is used or concealed, the permit holder runs a light test, passing a lamp of at least 100 watts through the entire duct to show the welds are tight (506.3.2.5). Air velocity stays at 500 feet per minute or more so grease travels rather than settles (506.3.4). Each Type I hood gets its own grease duct unless the hoods share one story and the same or adjoining rooms, cross no rated assembly and serve no solid-fuel appliance (506.3.5).

Clearances, enclosures and slope (506.3.6, 506.3.7, 506.3.11)

Where no enclosure is required, a grease duct keeps 18 inches from combustible construction and 3 inches from noncombustible construction, including gypsum board on noncombustible structure (506.3.6). A duct that penetrates a ceiling, wall, floor or concealed space is enclosed from the point of penetration to the outlet, in a shaft, a listed field-applied wrap or a factory-built enclosure. The enclosure is rated at least 1 hour and not less than the assembly it penetrates, and it holds only that one duct (506.3.11). No enclosure is needed for a duct that penetrates only a non-rated roof or ceiling assembly. Inside a shaft the clearances become 18 inches to combustibles and 6 inches to noncombustibles (506.3.11.1). Fire dampers and smoke dampers are not installed in grease ducts. Every cleanout inside an enclosure needs an access panel marked ACCESS PANEL. DO NOT OBSTRUCT. (506.3.12). The duct slopes at least 1/4 inch per foot (2 percent) toward the hood or a grease reservoir, and 1 inch per foot where a horizontal run exceeds 75 feet (506.3.7).

Cleanouts and reservoirs (506.3.7.1, 506.3.8, 506.3.9)

Grease has to be reachable. Horizontal cleanouts are spaced no more than 20 feet apart and no more than 10 feet from a change in direction over 45 degrees. Each opening is at least 12 by 12 inches, with a liquid-tight steel door, a gasket rated for 1,500 degrees F, and no fasteners through the duct. A reservoir sits at the bottom of a horizontal duct or riser, is at least 12 inches long and 1 inch deep across the full width, slopes to a drain and has its own cleanout (506.3.7.1). An in-line fan has cleanouts on both sides within 3 feet (506.3.8.2), and a duct big enough to enter needs a 22 by 20 inch opening (506.3.8.1).

Key numbers
  • Type I hood steel No. 18 gage; grease duct steel No. 16 gage or stainless No. 18 gage (507.2.3, 506.3.1.1)
  • Hood clearance 18 in. to combustibles; canopy overhang 6 in.; lip 4 ft maximum above the cooking surface (507.2.6, 507.4.1)
  • Filters at 45 degrees or steeper; lowest edge 6, 24 or 42 in. above the surface by fuel (507.2.8)
  • Exhaust rates by heaviest duty and hood type, cfm per linear foot (507.5); heaviest appliance governs
  • Duct velocity 500 fpm minimum; slope 1/4 in. per ft, or 1 in. per ft over 75 ft of horizontal run (506.3.4, 506.3.7)
  • Unenclosed duct clearance 18 in. and 3 in.; in a shaft 18 in. and 6 in.; enclosure 1 hour minimum (506.3.6, 506.3.11)
  • Cleanouts 20 ft apart maximum, 10 ft from turns over 45 degrees, 12 x 12 in. minimum (506.3.9)
  • Outlet 40 in. above roof, 10 ft from buildings and lot lines, 10 ft above grade (506.3.13)

Fans and outlets (506.3.13 and 506.5)

Fan housings are built like the duct unless listed to UL 762, and the motor stays out of the airstream (506.5.1). Upblast fans are hinged, on flexible weatherproof cable with a restraint, and the duct rises at least 18 inches above the roof (506.5.4). The discharge opening is at least 40 inches above the roof surface (506.3.13.1). The outlet stays at least 10 feet horizontally from the same or adjacent buildings and property lines and at least 10 feet above adjoining grade, and it is either 10 feet horizontally from or 3 feet above air intakes; where the discharge is directed away from those places, the horizontal distances drop to 5 feet (506.3.13.3). A wall termination is allowed only where it creates no nuisance or fire hazard, not where the IBC requires protected openings, and not within 3 feet of a wall opening (506.3.13.2). Type II hood outlets differ: 30 inches above the roof and from vertical walls, 3 feet from openings, 10 feet from lot lines and above grade (506.4.2).

Makeup air, testing and suppression (507.6, 508, 509)

Makeup air is supplied whenever the exhaust runs. The total supplied is about equal to the total exhaust, without weakening capture, and mechanical makeup starts automatically with the exhaust (508.1). Its temperature stays within 10 degrees F of the space unless the HVAC system can carry the load (508.1.1), and the plans show an air balance schedule (508.1.2). The hood fan starts automatically with the appliances or is interlocked to them (507.1.1). Before final approval the permit holder tests exhaust and makeup airflow and capture and containment with appliances hot, judged with smoke or steam (507.6). Appliances under a Type I hood also get an approved automatic fire suppression system under the IBC and IFC (509.1).

In the field

A church fellowship hall remodel adds a fryer and a gas range under a hood that is meant to be reused from a residential kitchen, with a flexible duct running into the attic. Check before anything is concealed: the hood is Type I and meets 507.5, the duct is welded No. 16 gage steel with no flex, the duct is enclosed where it crosses the ceiling, and the light test is done. Then walk outside: the outlet must be 40 inches above the roof and 10 feet from the neighboring building and every air intake.

Practice questions

1. Under 2021 IMC 507.2, a Type I hood is required over which appliance in a school cafeteria kitchen?

  1. A dishwasher
  2. A gas open-burner range
  3. A compartment steamer
  4. A hot water urn

2. An inspector finds a restaurant grease duct made of carbon steel that measures 0.0466 inch (No. 18 gage) with welded seams. What is the minimum thickness for carbon steel grease duct under 506.3.1.1?

  1. No. 22 gage (0.0296 inch)
  2. No. 20 gage
  3. No. 18 gage (0.0466 inch), the same as the hood
  4. No. 16 gage (0.0575 inch)

3. A 40-foot horizontal run of grease duct must slope at least how much under 506.3.7?

  1. 1/4 inch per foot toward the hood or a reservoir
  2. 1/8 inch per foot away from the hood, toward the fan
  3. 1 inch per foot toward the fan, since the run is over 20 feet
  4. It may be level if the duct is welded liquid tight

4. A horizontal grease duct run is 90 feet long. Under 506.3.7 its minimum slope is:

  1. 1/4 inch per foot
  2. 1/2 inch per foot
  3. 1 inch per foot
  4. 2 inches per foot

5. An unenclosed grease duct serving a Type I hood in a Group A-2 restaurant must keep what minimum clearance to combustible construction?

  1. 3 inches
  2. 6 inches
  3. 12 inches
  4. 18 inches

6. A 12-foot wall-mounted canopy hood covers a heavy-duty broiler and medium-duty fryers. Using 400 cfm per linear foot for heavy duty, the minimum net exhaust is:

  1. 3,600 cfm
  2. 4,800 cfm
  3. 6,600 cfm
  4. 7,200 cfm

7. Horizontal grease duct cleanouts are spaced no farther apart than:

  1. 10 feet
  2. 12 feet
  3. 20 feet
  4. 40 feet

8. A grease duct serving a Type I hood in a Group A-2 restaurant penetrates a 1-hour rated ceiling. Which protection follows 506.3.11?

  1. Enclose the duct from the penetration to the outlet, rated at least 1 hour
  2. Install a 1 1/2-hour fire damper where the duct passes the ceiling
  3. Install a combination fire and smoke damper at the ceiling
  4. No protection is needed because the duct is welded steel

9. An upblast fan on a grease duct discharges above a flat roof. The discharge opening must be at least how far above the roof surface (506.3.13.1)?

  1. 18 inches
  2. 40 inches
  3. 30 inches
  4. 10 feet

10. A canopy-type Type I hood must overhang the edge of the appliance at least 6 inches on open sides. The hood's front lower lip may be no more than what distance above the cooking surface?

  1. 2 feet
  2. 3 feet
  3. 5 feet
  4. 4 feet

11. A restaurant's Type I hood is complete. Before final approval, the permit holder must perform which test under 507.6?

  1. Only a visual check of the hood and its filters by the owner
  2. A hydrostatic water test of the duct before it is enclosed
  3. A capture and containment test with appliances hot and makeup air running
  4. No test is required for hoods that have listed filters installed

12. Makeup air for a commercial kitchen exhaust system must be within how many degrees Fahrenheit of the space temperature, unless the HVAC system can carry the added load (508.1.1)?

  1. 10 degrees
  2. 20 degrees
  3. 30 degrees
  4. 50 degrees

13. Unless the discharge is directed away, a Type I grease duct outlet must be at least how far horizontally from an adjacent property line (506.3.13.3)?

  1. 3 feet
  2. 10 feet
  3. 5 feet
  4. 30 feet

14. Grease filters in a Type I hood must be installed at an angle from the horizontal of not less than:

  1. 15 degrees
  2. 30 degrees
  3. 45 degrees
  4. 90 degrees

Glossary

Type I hood
A hood for cooking that produces grease or smoke; the whole system behind it is built as a grease exhaust system.
Type II hood
A hood for heat, steam or combustion products without grease, such as over a dishwasher; built to lighter rules.
Duty classification
The light, medium, heavy or extra-heavy rating of a cooking appliance, which sets the exhaust rate and hood requirements.
Grease duct
The welded steel duct that carries grease-laden air from a Type I hood to the outdoors.
Grease reservoir
A low point in the duct that collects grease, with a drain and its own cleanout.
Makeup air
Outdoor air supplied to replace what the exhaust removes, so the kitchen does not go into negative pressure.
Capture and containment
The hood's ability to hold cooking vapors under the canopy, checked in the field with smoke or steam.
Light test
A leak test in which a bright lamp passed through the duct shows any gap at a weld or joint.