IRC E3902 (NEC 210.8, 210.12) · 14 practice questions
0:00 / --:--
Reading
This lesson covers two different protection systems that both live in E3902 but do different jobs
and are triggered by different locations. A ground-fault circuit interrupter, GFCI, protects people
from shock by shutting a circuit off the instant current is leaking somewhere it should not be, such as
through a person's body to ground. An arc-fault circuit interrupter, AFCI, protects the building from
fire by detecting the electrical signature of a damaged or loose connection arcing inside a wall before
it gets hot enough to ignite framing or insulation. A room can require one, the other, both, or
neither, and mixing the two up is one of the most common mistakes staff make when reviewing an
electrical scope.
GFCI-required locations
E3902 lists the dwelling locations where 125-volt through 250-volt receptacles on single-phase
circuits of 150 volts or less to ground must be GFCI protected (NEC 210.8(A)): bathrooms (E3902.1);
garages, and the grade-level portions of unfinished accessory buildings used for storage or work
(E3902.2); outdoors (E3902.3); crawl spaces at or below grade, where lighting outlets also need GFCI
protection (E3902.4); basements (E3902.5); kitchens, where the receptacle serves countertop surfaces
(E3902.6); any receptacle within 6 feet of the top inside edge of a sink bowl (E3902.7); any receptacle
within 6 feet of the outside edge of a bathtub or shower stall (E3902.8); laundry areas (E3902.9);
indoor damp or wet locations (E3902.10); and boathouses (E3902.12). Because the range runs through
250 volts, a dryer or range receptacle falls in scope where it sits in one of these locations, a
basement or garage for example. Two rules sit outside that list: E3902.11 requires GFCI protection for
outlets on branch circuits of 150 volts or less to ground that supply dishwashers, wherever in the
dwelling they are installed, and E3902.16 requires it for the HVAC servicing receptacle from Lesson 5.
Distances are measured along the shortest path a cord would follow without piercing a wall, floor,
or fixed barrier (E3902.18).
Outdoor outlets
A separate provision, E3902.17 (NEC 210.8(F)), requires GFCI protection for all outdoor outlets, not
only receptacles, supplied by single-phase branch circuits of 150 volts to ground or less and 50
amperes or less. Its exception is for lighting outlets other than crawl space lighting, and E3902.3
excepts a receptacle that is not readily accessible and is on a dedicated branch circuit for electric
snow-melting or deicing equipment (E4101.7). Editions differ in how they word the outdoor rule, so a
house built or permitted under an earlier adopted edition may not have this protection, and that is
not automatically a violation of the code that applied at the time. New work is different: additions,
alterations, and repairs must meet the code adopted now (R102.7.1).
AFCI-required areas
E3902.20 (NEC 210.12(A)) requires AFCI protection on all 120-volt, single-phase, 15- and
20-ampere branch circuits supplying outlets in dwelling unit kitchens, family rooms, dining
rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways,
laundry areas, or similar rooms or areas. In practical terms, this covers nearly every finished living space in the house. Areas the section
does not name, such as bathrooms, garages, unfinished basements, and crawl spaces, are not on the AFCI
list, though a finished basement recreation room is covered because a recreation room is named.
How AFCI protection is provided
The most common method is a listed combination-type AFCI circuit breaker at the panel, which protects
the entire branch circuit from the panel out (the first option in E3902.20). The other options use a
listed outlet branch-circuit type AFCI at the first outlet, each with its own conditions, for example
paired with a branch/feeder AFCI at the origin, or where the run from the panel to the first outlet is
metal raceway, Type MC or AC cable with metal boxes, or conduit encased in at least 2 inches of
concrete. For an existing circuit that is modified, replaced, or extended in the listed areas,
E3902.21 allows either a combination-type AFCI at the origin or an outlet branch-circuit type AFCI at
the first receptacle outlet of the existing circuit, and it exempts an extension of 6 feet or less
that adds no outlets or devices other than splices. This alternative matters constantly in GCHS rehab work, where an older panel is being reused rather
than replaced and a full breaker swap is not part of the scope.
Where both protections apply to the same circuit
Kitchen and laundry circuits are the clearest example of a circuit that needs both protections at
once: E3902.6 and E3902.9 require GFCI on the countertop and laundry-area receptacles, while E3902.20
separately requires AFCI because kitchens and laundry areas are named areas in that section. The two
requirements do not cancel each other out or let one substitute for the other. A dual-function breaker
that provides both GFCI and AFCI protection in a single device is the common way to satisfy both
requirements without stacking two breakers or adding a downstream receptacle-type device, and it is
worth specifically asking about on any GCHS kitchen or laundry room scope.
Tamper-resistant receptacles, a related but separate rule
Tamper-resistant receptacles are a physical shutter feature built into the receptacle itself, not an
electronic protection device, and they are required for 15- and 20-ampere, 125- and 250-volt nonlocking receptacles in the areas covered by
E3901.1, with a few exceptions such as receptacles more than 5.5 feet above the floor (E4002.14),
regardless of GFCI or AFCI status. They are covered in depth in Lesson
10 alongside other device requirements; the reason to flag them here is that a receptacle needing GFCI
or AFCI protection almost always also needs to be tamper-resistant, and inspectors frequently check
for both features on the same device at the same time.
Key numbers
GFCI locations (E3902.1 to E3902.12): bathrooms, garages and grade-level accessory building work areas, outdoors, crawl spaces at or below grade, basements, kitchen countertop receptacles, within 6 ft of a sink bowl, boathouses, within 6 ft of a tub or shower, laundry areas, damp/wet locations
GFCI scope covers 125-volt through 250-volt receptacles on single-phase circuits of 150 V or less to ground
Outdoors (E3902.17): GFCI on all outdoor outlets at 150 V to ground or less and 50 A or less, not only receptacles; lighting outlets excepted
Dishwashers (E3902.11): GFCI for outlets on branch circuits of 150 V or less to ground that supply dishwashers, wherever installed, separate from the location list
AFCI areas (E3902.20): kitchens, family/dining/living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, similar rooms
AFCI provided by a combination-type breaker, or a listed outlet branch-circuit AFCI at the first outlet where E3902.20 or E3902.21 allows it
Kitchen and laundry circuits commonly need both GFCI and AFCI, often via a dual-function breaker
A worked example: a rehab job rewires a kitchen with a dedicated small-appliance circuit feeding the
countertop receptacles, and a separate circuit for the laundry area next to it. Both circuits serve
areas named in E3902.20, so both need AFCI protection. Both circuits also feed receptacles covered by
E3902.6 and E3902.9, countertop receptacles and the laundry-area receptacle, so both also need GFCI protection.
The panel being reused is an older model that does accept AFCI breakers, so the simplest compliant
choice is two dual-function AFCI/GFCI breakers, one per circuit, rather than an AFCI breaker paired with
a separate GFCI receptacle on each circuit.
In the field
A frequent finding on GCHS inspections of older houses is a bathroom or kitchen receptacle that has
been replaced at some point with a modern-looking device that is not actually GFCI protected, because
the replacement receptacle itself has no test or reset button and there is no GFCI breaker or upstream
GFCI receptacle feeding it. A quick plug-in tester at each bathroom, kitchen, and outdoor receptacle
during a walkthrough catches this in under a minute per outlet, long before it becomes a change order
during construction.
Kitchen and laundry areas are the clearest examples of rooms that trigger both GFCI and AFCI protection on the same circuit.
Practice questions
1. A GFCI device is primarily intended to protect against:
Overloaded conductors
Electric shock from current leaking to ground
Arcing at loose connections that could start a fire inside a wall
Voltage drop on long runs
Answer: b. A GFCI compares current going out on the hot conductor to current returning on the neutral and trips on the small imbalance that shows current is leaking somewhere else, commonly through a person.
2. An AFCI device is primarily intended to protect against:
Shock from a leaking circuit, such as current passing through a person to ground
Overvoltage from the utility
Fire from arcing at a damaged or loose connection
Overloaded neutrals on multiwire circuits
Answer: c. AFCI protection recognizes the electrical signature of arcing, such as at a loose terminal or a nail through a cable, and interrupts the circuit before that heat starts a fire.
3. Under IRC E3902, which of these is NOT one of the locations requiring GFCI protection?
Bathrooms
Basements
Kitchen countertop receptacles
Bedrooms
Answer: d. Bedrooms are an AFCI-required area under E3902.20, not a location named in the GFCI list; a bedroom receptacle does not need GFCI protection simply for being a bedroom.
4. Under IRC E3902, GFCI protection at the listed dwelling locations covers receptacles rated:
125 to 250 volts, on single-phase circuits of 150 volts or less to ground
Only lighting outlets on circuits of 120 volts or less within 6 feet of a sink
Only three-phase circuits
Only commercial kitchens
Answer: a. E3902 applies to 125-volt through 250-volt receptacles on single-phase circuits of 150 volts or less to ground, which brings some dryer and range receptacles in listed locations into scope.
5. Under E3902.17, GFCI protection is required for:
Only indoor receptacles
All outdoor outlets of 50 amperes or less, not only receptacles, except lighting outlets
Only 240-volt outdoor equipment
Only outdoor receptacles rated 15 or 20 amperes, with no exceptions of any kind for other outlets
Answer: b. E3902.17 reaches outdoor outlets generally, not only receptacle outlets, up to 50 amperes, with an exception for lighting outlets other than crawl space lighting.
6. Under E3902.20, AFCI protection is required for branch circuits supplying outlets in all of these EXCEPT:
Bedrooms and the closets and hallways serving them
Living rooms
Unfinished, storage-only crawl spaces
Hallways
Answer: c. An unfinished, storage-only crawl space is not one of the living-space areas named in E3902.20; bedrooms, living rooms, and hallways all are.
7. The most common way to provide AFCI protection for a full branch circuit is:
A GFCI receptacle at the first outlet
A combination-type AFCI circuit breaker at the panel
A surge protective device at the service
A tamper-resistant receptacle
Answer: b. A combination-type AFCI breaker protects the entire circuit from the panel outward, which is the usual method in new work.
8. A rehab job reuses an older panel that cannot accept AFCI breakers, and an existing bedroom circuit is being extended with new outlets. An alternative that E3902.21 allows is:
A listed outlet branch-circuit AFCI at the first outlet of the existing circuit
Skipping AFCI protection since the panel is old and the circuit was wired before AFCI rules
A standard GFCI receptacle instead
A larger breaker
Answer: a. E3902.21 permits a listed outlet branch-circuit type AFCI at the first receptacle outlet of the existing circuit in place of a combination-type AFCI at the origin, so the panel breaker need not be replaced.
9. A kitchen small-appliance circuit feeding countertop receptacles requires:
GFCI only, since kitchens are named under E3902.6 but are not an AFCI area
AFCI only, since GFCI applies only to bathrooms
Neither, since it is a dedicated circuit
Both GFCI and AFCI protection, since the kitchen is named in both sections
Answer: d. Kitchens appear on both lists, so a kitchen countertop circuit needs both protections, commonly provided together by a dual-function breaker.
10. An inspector finds a laundry-area receptacle circuit protected only by a standard, non-GFCI, non-AFCI breaker. The correct finding is:
Compliant, since laundry areas have no special protection rule beyond the branch-circuit rating
A violation, since laundry areas require both GFCI (E3902.9) and AFCI (E3902.20) protection
A violation of GFCI rules only
A violation of AFCI rules only
Answer: b. Laundry areas are named under both sections, so this circuit is missing both required forms of protection, not just one.
11. A garage used only for parking and storage, with a floor at grade, needs which protection at its receptacles?
GFCI, since garages are a named GFCI location
AFCI, since garages are a named AFCI area
Both GFCI and AFCI
Neither
Answer: a. Garages (E3902.2) are named in the GFCI list; an ordinary storage garage is not one of the living-space areas named for AFCI.
12. A tamper-resistant receptacle differs from a GFCI receptacle in that it:
Also provides arc-fault protection
Is only required outdoors
Provides a physical shutter against foreign objects and carries no electronic shock or arc protection
Replaces the need for GFCI protection in bathrooms, because the shutters keep a person from contacting live parts
Answer: c. Tamper resistance is a mechanical feature covered in Lesson 10; it does not substitute for the electronic protection a GFCI or AFCI device provides, and most locations need both features on the same device.
13. A finished basement recreation room with a wet bar sink is being evaluated. Which protections likely apply?
GFCI only, since basements are a GFCI location and a wet bar is the only sink-related trigger
AFCI only
Neither, since it is below grade
Both GFCI, for the basement and the sink, and AFCI, since a recreation room is a named area
Answer: d. Basements and receptacles within 6 feet of a sink both trigger GFCI, and a finished recreation room is specifically named as an AFCI area, so both apply at once.
14. A house was built under an older adopted edition of the code. During a rehab, an inspector finds existing, untouched outdoor outlets that do not meet E3902.17. The correct response is:
Existing work is not automatically a violation (R102.7), but new or altered outlets must meet the current code (R102.7.1)
Automatically fail the house under the current code, regardless of when it was built or whether any work touches those outlets
Ignore GFCI requirements for any older house
Assume the local jurisdiction never adopted the 2021 code
Answer: a. R102.7 lets existing structures continue in use, while R102.7.1 requires additions, alterations, and repairs to conform to the requirements for new work; GCHS staff also verify the edition and amendments the jurisdiction has adopted.
Glossary
GFCI
Ground-fault circuit interrupter; a device that compares outgoing and returning current on a circuit and trips on the small imbalance caused by current leaking to ground, protecting people from shock.
AFCI
Arc-fault circuit interrupter; a device that detects the electrical signature of arcing at a damaged or loose connection and interrupts the circuit before it can ignite nearby material.
Combination-type AFCI
An AFCI device designed to detect both series and parallel arcing faults, the type E3902.20 lists first as protecting the entire branch circuit.
Outlet branch-circuit AFCI
A listed AFCI receptacle installed at the first outlet position that protects the downstream portion of a circuit, used where E3902.20 or E3902.21 allows it, for example where the panel cannot accept an AFCI breaker on an existing circuit.
Dual-function breaker
A single circuit breaker providing both GFCI and AFCI protection, commonly used on circuits such as kitchen and laundry circuits that require both.
Tamper-resistant receptacle
A receptacle with internal shutters that block insertion of a single object into one slot; a physical safety feature covered fully in Lesson 10, separate from GFCI and AFCI protection.