Commercial Electrical 100%

2023 NEC Articles 430 and 440

Lesson 11: Motors and Air-Conditioning Equipment

NEC 430, 440, 210.63 · 14 practice questions

0:00 / --:--

Reading

Motors change how a circuit is sized. A motor pulls several times its running current for a moment at start, so its branch circuit is built from separate parts, and each part has its own rule: conductors, short-circuit and ground-fault protection, overload protection, controller, and disconnect. Air-conditioning equipment adds a nameplate that does most of the arithmetic for you. This lesson covers Article 430 for general motors and Article 440 for air-conditioning and refrigeration equipment, with one worked motor example and one rooftop unit. Local adoption governs which edition applies (see Lesson 1).

Rooftop unit checkpoints and a motor branch circuit sizing example On the left, a rooftop air-conditioning unit sits on a roof curb. Its nameplate shows a minimum circuit ampacity of 24 amperes and a maximum overcurrent protective device of 40 amperes. A disconnect is within sight of the unit, not more than 50 feet away, and a GFCI service receptacle is within 25 feet on the same level. On the right, a 15 horsepower, 460 volt, 3-phase motor has a table full-load current of 21 amperes. The breaker may be 250 percent, 52.5 amperes, so the next size, 60 amperes. The disconnect must be at least 115 percent, 24.2 amperes, so 30 amperes. The overload is at most 125 percent of the 19.6 ampere nameplate, 24.5 amperes. The conductors are at least 125 percent of 21 amperes, 26.3 amperes, so 10 AWG copper. Air-conditioning unit and motor circuit (not to scale) Rooftop unit (Article 440) Motor branch circuit (Article 430) Nameplate MCA 24 A MOCP 40 A Rooftop unit Disc. In sight, 50 ft max 1 2 3 4 1. Conductors at least MCA, 24 A (440.35): 10 AWG copper, 30 A at 60 C (Table 310.16) 2. Breaker not over MOCP, 40 A (440.4(B)) 3. Disconnect in sight, ready access (440.14) 4. GFCI receptacle within 25 ft, same level (210.63(A), 210.8(E)) MCA and MOCP come from the unit nameplate. 15 hp, 460 V, 3-phase, nameplate 19.6 A, SF 1.15 Breaker Disconnect Overload Conductors 15 hp motor Inverse-time breaker, max 250%: 2.5 x 21 A = 52.5 A, next size 60 A Table 430.52(C)(1), (C)(1)(a) In sight; at least 115% of FLC: 1.15 x 21 A = 24.2 A, use 30 A 430.102, 430.110(A) From nameplate current, SF 1.15: 1.25 x 19.6 A = 24.5 A maximum 430.6(A)(2), 430.32(A)(1) At least 125% of table FLC: 1.25 x 21 A = 26.3 A 10 AWG Cu, 30 A at 60 C (430.22) Table full-load current, 460 V: 21 A for 15 hp Table 430.250, 430.6(A)(1) Table values size conductors, switch, and breaker. The nameplate sizes the overload.
Left, what to check at a rooftop unit: nameplate MCA and MOCP, conductors, breaker, disconnect within sight, and the service receptacle. Right, the parts of a motor branch circuit and the number each one is sized from.
Two checks from the rooftop unit nameplateThe existing rooftop unit example has MCA 24 amperes and MOCP 40 amperes. One branch checks conductor ampacity against the minimum; the other checks the protective device against the maximum. Rooftop unit nameplateMCA 24 AMOCP 40 AConductor ampacityAt least 24 ACompare with MCAProtective deviceNo more than 40 ACompare with MOCPExisting lesson example. Read the actual equipment nameplate.
The two values answer different questions in the existing rooftop unit example. Conductors meet or exceed MCA; the breaker or fuse does not exceed MOCP. See the lesson for conductor selection and installation checks.

Which current to use

A motor has two currents. One is marked on its nameplate. The other comes from the NEC tables for its horsepower, voltage, and phase: Table 430.248 for single-phase motors and Table 430.250 for 3-phase induction motors. For general motor applications, the table value sets the conductor ampacity, the switch rating, and the short-circuit and ground-fault protection. The nameplate current sets the separate overload protection (2023 NEC 430.6(A)(1) and (A)(2)). Using the wrong one is the most common arithmetic error in motor plan review. Motors built for low speeds, high torques, or multispeed operation are exceptions that use the nameplate for more items, and that is why the nameplate is always read too.

Horsepower (3-phase induction)208 V230 V460 V
516.7 A15.2 A7.6 A
1030.8 A28 A14 A
1546.2 A42 A21 A
2059.4 A54 A27 A

Motor conductors

Conductors that supply a single continuous-duty motor need an ampacity of at least 125 percent of the table full-load current (430.22). A 20 hp, 460 V motor has a table current of 27 A, so its conductors need 33.75 A of ampacity. Then Table 310.16 and the termination rules of Lesson 8 and Lesson 2 pick the conductor. For circuits of 100 A or less, equipment terminals are treated as 60 C unless the equipment is marked otherwise, so the 60 C column is the safe place to look (110.14(C)(1)(a)).

Short-circuit and ground-fault protection

The branch-circuit device protects against short circuits and ground faults, not overloads, so it is allowed to be much larger than the motor current. It has to carry the starting surge. The maximum comes from Table 430.52(C)(1), as a percentage of the table full-load current. If the result is not a standard rating in 240.6, the next higher standard rating is permitted (430.52(C)(1)(a)).

Device (squirrel-cage motor)Maximum, percent of full-load current
Nontime-delay fuse300
Dual-element (time-delay) fuse175
Inverse-time circuit breaker250
Instantaneous-trip breaker (part of a listed combination controller)800

If the device still trips when the motor starts, 430.52(C)(1)(b) allows more, but never beyond a hard ceiling: 400 percent for a nontime-delay fuse up to 600 A, 225 percent for a dual-element fuse, and for an inverse-time breaker 400 percent when the motor current is 100 A or less and 300 percent when it is over 100 A. The ceiling is a maximum, so the next-higher-size rule does not apply after it.

Overload protection

An overload device protects the motor from running too long above its rating. Using the nameplate current, a separate overload device may be set at no more than 125 percent for motors with a marked service factor of 1.15 or more, or a marked temperature rise of 40 C or less, and 115 percent for all others (430.32(A)(1)). If that setting will not let the motor start or carry its load, the device may be raised to 140 percent or 130 percent, respectively (430.32(C)).

Disconnecting means

Each motor controller needs a disconnect in sight from the controller, and the motor itself needs a disconnect in sight from both the motor and the driven machinery, unless the controller disconnect is in sight of the motor and serves both (430.102). Article 100 defines in sight as visible and not more than 50 ft away. The motor disconnect may be left out when the controller disconnect is lockable and in-sight placement is impracticable or adds hazard, such as motors over 100 hp, multimotor equipment, submersible motors, and motors on adjustable-speed drives, or in industrial installations with written safety procedures (430.102(B)(2)). The disconnect must have a current rating at least 115 percent of the motor full-load current, unless it is a listed unfused motor-circuit switch with a horsepower rating at least equal to the motor's (430.110(A)). Disconnect types include hp-rated motor-circuit switches, molded case breakers and switches, and manual motor controllers marked as suitable for use as a motor disconnect (430.109(A)).

Air-conditioning nameplates: MCA and MOCP

Article 440 covers equipment with a hermetic refrigerant motor-compressor. Multimotor and combination-load equipment, such as a packaged rooftop unit, must be marked with its minimum supply circuit conductor ampacity (MCA) and the maximum rating of its short-circuit and ground-fault protective device (MOCP) (440.4(B)). Conductors supplying the unit must have an ampacity not less than the MCA (440.35), and the breaker or fuse must not exceed the MOCP (440.4(B), 440.22(B)). The nameplate does the arithmetic once, so the field check is a comparison: conductor at or above MCA, protective device at or below MOCP.

Single compressors and the disconnect

For a single hermetic compressor, use the rated-load current on the equipment nameplate, or the branch-circuit selection current where one is marked, in place of the motor tables (440.6(A)). Conductors need at least 125 percent of that current (440.32). The short-circuit device may be up to 175 percent, and up to 225 percent if that will not start the compressor, with a floor of 15 A that the device need not go below (440.22(A)). The disconnect rating must be at least 115 percent of the same current (440.12(A)(1)).

Location, receptacles, and rooftops

The disconnect must be within sight of and readily accessible from the equipment, and may be mounted on or inside it. It needs the working space of 110.26(A), and it may not sit on a panel that must be removed to service the equipment or cover the nameplate (440.14). On the roof, a 125 V, 15 or 20 A receptacle for servicing must be within 25 ft of the unit, on the same level, and not on the load side of the unit disconnect (210.63(A)), with GFCI protection (210.8(E)). Conductors in sunlight must be sunlight resistant (310.10(D)), and a raceway or cable less than 3/4 in. above the roof takes a 33 C temperature adder for ampacity correction, except type XHHW-2 (310.15(B)(2)). Raising the conduit off the roof avoids the adder.

Worked example: a 15 hp motor and a rooftop unit

A GCHS community center adds a 15 hp, 460 V, 3-phase exhaust fan motor with a nameplate current of 19.6 A and a marked service factor of 1.15. Table 430.250 gives 21 A. Conductors: 21 x 1.25 = 26.25 A, so 10 AWG copper, rated 30 A in the 60 C column. Short-circuit protection with an inverse-time breaker: 21 x 2.5 = 52.5 A, so the next standard size, 60 A, is the largest allowed. Overload: 19.6 x 1.25 = 24.5 A maximum. Disconnect: 21 x 1.15 = 24.15 A, so a 30 A switch, in sight of the motor.

The rooftop unit on the same building is marked MCA 24 A and MOCP 40 A. The conductors need at least 24 A, so 12 AWG copper (20 A) is too small and 10 AWG (30 A at 60 C) is the smallest that works. The breaker may not exceed 40 A. The disconnect goes within sight of the unit, and the service receptacle within 25 ft on the roof.

Key numbers
  • Motor conductors: 125 percent of table full-load current (430.22)
  • Inverse-time breaker: up to 250 percent; dual-element fuse 175; nontime-delay fuse 300 (Table 430.52(C)(1))
  • Overload: 125 percent of nameplate with service factor 1.15 or more, otherwise 115 (430.32(A)(1))
  • Motor disconnect: at least 115 percent of full-load current (430.110(A)); in sight means visible and within 50 ft
  • Rooftop unit: conductors at or above MCA, protective device at or below MOCP (440.35, 440.4(B))
  • Single compressor: conductors 125 percent, device 175 percent, disconnect 115 percent (440.32, 440.22(A), 440.12(A)(1))
  • Service receptacle: within 25 ft, same level, GFCI protected (210.63(A), 210.8(E))

In the field

A GCHS rehab replaces the failed rooftop unit on a small clinic. The new unit is one size larger, and the old 30 A breaker is still there. The inspector reads the new nameplate first: MCA 24 A, MOCP 40 A. The old conductors are 10 AWG, which is enough. The breaker is under the maximum, so it can stay. Then the walk: the disconnect is within sight but is screwed to the service panel that the technician removes to reach the compressor, and the service receptacle is 60 ft across the roof. Both get corrected before the unit is approved.

Practice questions

1. A Group B building has a 10 hp, 208 V, 3-phase squirrel-cage motor that runs continuously. Using Table 430.250 and 430.22, what is the minimum ampacity of its branch-circuit conductors?

  1. 30.8 A, because the table current is the conductor ampacity
  2. 38.5 A, which is 125 percent of the 30.8 A table current
  3. 35.4 A, which is 115 percent of the 30.8 A table current
  4. 44.0 A, which is 125 percent of a 35.2 A nameplate current

2. A 15 hp, 460 V, 3-phase squirrel-cage motor in a community center mechanical room has a nameplate current of 19.4 A. Which current is used to size its branch-circuit conductors?

  1. The 19.4 A nameplate value, because it is the actual current the motor draws
  2. The 19.4 A nameplate value, but only when the motor is over 10 hp
  3. The average of the nameplate and table values, which is 20.2 A
  4. The 21 A table value from Table 430.250, because 430.6(A)(1) uses the table for conductors

3. A 10 hp, 460 V motor in a Group F shop has a nameplate current of 13.2 A and a marked service factor of 1.15. What is the largest setting for a separate overload relay under 430.32(A)(1)?

  1. 16.5 A, which is 125 percent of the 13.2 A nameplate current
  2. 15.2 A, which is 115 percent of the 13.2 A nameplate current
  3. 17.5 A, which is 125 percent of the 14 A table current
  4. 18.5 A, which is 140 percent of the 13.2 A nameplate current

4. An inverse-time circuit breaker will protect a 20 hp, 460 V squirrel-cage motor, which has a table current of 27 A. What is the largest standard breaker allowed by Table 430.52(C)(1) and 430.52(C)(1)(a)?

  1. 60 A, because a device may never be larger than the calculated value
  2. 90 A, because 300 percent of 27 A is 81 A and the next standard size above that is 90 A
  3. 70 A, because 250 percent of 27 A is 67.5 A and the next standard size is 70 A
  4. 110 A, because 400 percent of 27 A is 108 A and the next size is 110 A

5. A dual-element fuse protects a 5 hp, 208 V, 3-phase squirrel-cage motor with a table current of 16.7 A. What is the largest standard fuse under Table 430.52(C)(1) and the next-higher-size rule?

  1. 25 A, because 150 percent of 16.7 A is 25 A
  2. 40 A, because 250 percent of 16.7 A is 41.8 A, which rounds down to a standard 40 A rating
  3. 50 A, because 300 percent of 16.7 A is 50.1 A
  4. 30 A, because 175 percent of 16.7 A is 29.2 A and the next standard size is 30 A

6. A 10 hp, 460 V motor has a table current of 14 A. The 35 A inverse-time breaker trips every time the motor starts. What is the largest standard breaker that 430.52(C)(1)(b) permits?

  1. 60 A, because the next higher standard size above 56 A is allowed under the next-size rule
  2. 50 A, because the breaker may not exceed 400 percent of 14 A, which is 56 A
  3. 45 A, because the breaker may be raised only to 300 percent of 14 A
  4. 70 A, because 500 percent is allowed when the motor will not start

7. A 15 hp, 460 V motor in a Group B building has a table current of 21 A, and the disconnect is a fusible switch that is not an hp-rated motor-circuit switch. What is the minimum ampere rating of the switch under 430.110(A)?

  1. 21 A, because the switch must equal the motor full-load current
  2. 26.3 A, because the switch is sized like the conductors at 125 percent
  3. 30 A, because 115 percent of 21 A is 24.2 A and the next standard switch rating is 30 A
  4. 60 A, because the switch must match the 60 A branch-circuit breaker that protects the motor circuit

8. A 5 hp exhaust fan motor on the roof of a Group B building has a fused disconnect in the second-floor mechanical room, 80 ft away and out of sight of the motor. No exception applies. What is the finding under 430.102?

  1. The motor disconnect must be in sight of the motor and driven machinery, meaning visible and within 50 ft
  2. The disconnect is acceptable, because in sight allows up to 100 ft
  3. The disconnect is acceptable, because any lockable disconnect may be out of sight
  4. The disconnect is acceptable, because it is on the same circuit as the motor

9. A rooftop unit on a Group A-3 community building is marked MCA 24 A and MOCP 40 A. What is the smallest copper conductor that meets the MCA using the 60 C column of Table 310.16?

  1. 12 AWG, which is 20 A in the 60 C column
  2. 14 AWG, which is 15 A in the 60 C column
  3. 8 AWG, which is 40 A in the 60 C column
  4. 10 AWG, which is 30 A in the 60 C column

10. The nameplate of a rooftop unit on a Group B office reads MOCP 40 A. The installer wants to use a 50 A breaker because one is on the truck. What do 440.4(B) and 440.22(B) require?

  1. Allowed, because 175 percent of the compressor current replaces the nameplate
  2. Not allowed, because the branch-circuit device may not exceed the 40 A maximum on the nameplate
  3. Allowed, if the conductors are upsized to 6 AWG copper so that they match the 50 A breaker rating
  4. Allowed, if the disconnect is rated 60 A or more

11. During a final inspection of a Group B clinic, the disconnect for a rooftop unit is mounted on the panel that the technician removes to reach the compressor. What is the finding under 440.14?

  1. No finding, because a disconnect mounted on the unit is always acceptable wherever it is placed
  2. The disconnect must be at least 6 ft away from the unit in every case
  3. The disconnect may not sit on an access panel or where it hides the nameplate
  4. The disconnect is acceptable if the unit is also GFCI protected

12. A rooftop unit on a Group B building has its only service receptacle 40 ft away at the roof hatch, connected to the load side of the unit disconnect. What does 210.63(A) require?

  1. A 125 V, 15 or 20 A receptacle within 25 ft of the unit on the same level, not on the load side of the disconnect
  2. A receptacle within 50 ft, which is the in-sight distance for disconnects
  3. A receptacle within 25 ft, and it may be on the load side of the disconnect
  4. No receptacle, because a rooftop unit is served by a portable generator

13. A single hermetic compressor in a Group M walk-in cooler has a nameplate rated-load current of 17.9 A and no branch-circuit selection current marked. What is the minimum conductor ampacity under 440.32?

  1. 17.9 A, which is the rated-load current
  2. 20.6 A, which is 115 percent of the rated-load current
  3. 31.3 A, which is 175 percent of the rated-load current of the compressor
  4. 22.4 A, which is 125 percent of the 17.9 A rated-load current

14. A single hermetic compressor has a rated-load current of 17.9 A and is the only load on its circuit. What is the largest standard short-circuit device under 440.22(A), using the 175 percent value and the next-higher-size rule?

  1. 30 A, because the device may never exceed 31.3 A
  2. 35 A, because 175 percent of 17.9 A is 31.3 A and the next standard size is 35 A
  3. 40 A, because 225 percent of 17.9 A is 40.3 A, and a larger device is always allowed
  4. 45 A, because 250 percent of 17.9 A is 44.8 A

Glossary

Full-load current (table)
The current in Tables 430.248 and 430.250 for a given horsepower and voltage, used for motor conductors, switches, and short-circuit protection.
Overload protection
A device responsive to motor current that trips or is rated at no more than 115 or 125 percent of nameplate current (430.32).
Short-circuit and ground-fault protection
The branch-circuit breaker or fuse that clears faults and may be much larger than motor current so the motor can start (Table 430.52(C)(1)).
Within sight
Equipment that is visible and not more than 50 ft distant from other equipment (Article 100).
Minimum circuit ampacity (MCA)
The nameplate value that the supply conductors to multimotor or combination-load equipment must not be smaller than (440.4(B), 440.35).
Maximum overcurrent protective device (MOCP)
The nameplate value that the branch-circuit breaker or fuse must not exceed (440.4(B), 440.22(B)).
Rated-load current
The current marked on a hermetic compressor or its equipment nameplate, used with Article 440 instead of the motor tables (440.6(A)).
Service factor
A number marked on a motor showing how much overload it can carry; 1.15 or more allows an overload setting of 125 percent (430.32(A)(1)).