Lesson 12: Special Occupancies and Temporary Installations

NEC 500, 511, 514, 517, 518, 590 · 14 practice questions

0:00 / --:--

Reading

Chapter 5 of the NEC adds rules for places where fire, explosion, or patient safety is a special concern, and Article 590 adds rules for wiring that is not permanent. Most GCHS work is ordinary, but rehab and construction management put you in three of these places often: a church hall or community building that counts as assembly, a clinic with patient care spaces, and every job site during construction. Hazardous locations and health care are taught here at a pointer level, so you can recognize when they apply and know that a specialist reads the rest. Assembly and temporary installations are taught in more detail, including the GFCI rules for construction. Local adoption governs which edition applies (see Lesson 1).

Temporary power layout for a construction site with GFCI requirements A plan view. A temporary service pedestal outside a building under construction feeds a temporary panelboard inside. Three circuits leave the panelboard. The first supplies 125 volt, 15, 20 and 30 ampere tool receptacles that need GFCI protection for personnel under 590.6(A), with in-use covers in wet locations. The second supplies guarded temporary lamps and carries no receptacles. The third supplies 250 volt or 3-phase equipment such as a hoist or welder, which needs GFCI protection or a written assured equipment grounding conductor program. A portable generator of 15 kilowatts or less outside the building has 125 volt and 125/250 volt outlets that need listed GFCI protection. Notes state that cords are protected at doors, cables stay off the floor, and the wiring is removed when the work is done. Temporary power on a construction site, plan view (not to scale) Building under construction Temporary service (590.4(A)) Feeder (590.4(B)) Temporary panelboard GFCI Lamp 250 V 125 V, 15, 20, 30 A tool outlets: GFCI protection for personnel (590.6(A)) Wet locations: in-use covers (406.9(B)(1)) Temporary lighting circuit: lamps guarded (590.4(F)) no receptacles on it (590.4(D)(1)) 250 V or 3-phase hoist or welder: GFCI, or a written assured equipment grounding program (590.6(B)) Portable generator 15 kW or less Its 125 V and 125/250 V, 15, 20, 30 A outlets need listed GFCI protection (590.6(A)(3)) Cords protected at doors and pinch points (590.4(H)) Feeder and branch cables off the floor and ground (590.4(J)) Wiring removed when the work is done (590.3(D))
A construction site with each temporary circuit labeled by the protection it needs: GFCI for 125 V tool outlets and generator outlets, a separate guarded lighting circuit, and GFCI or a written program for 250 V and 3-phase receptacles.

Hazardous (classified) locations at a glance

Article 500 sorts hazardous places by what is in the air and how often. Class I is flammable gas or vapor. Class II is combustible dust. Class III is combustible fibers and flyings (500.5(B), (C), (D)). Within a class, Division 1 means the hazard can be present under normal operation, or because of frequent repair, leaks, or a breakdown that could also make the equipment a source of ignition. Division 2 means the material is normally confined in closed containers or systems and escapes only through accidental rupture, failure, or abnormal operation (500.5(B)(1) and (B)(2)). The classification, its extent, and the equipment permitted inside are set by the designer and the authority having jurisdiction, and the detailed wiring rules of the articles that follow Article 500 then apply. Your job is to spot the trigger: a fuel dispenser, a paint booth, a grain or flour room, or a repair garage.

Garages and fuel dispensing

Parking garages used only for parking or storage are permitted to be unclassified (511.3(A)). Repair garages are different: a garage that dispenses fuel follows 511.3(B), and one that repairs vehicles using Class I liquids or heavier-than-air gaseous fuels such as LPG follows Table 511.3(C). GFCI protection in commercial garages is required as 210.8(B) says (511.12). A gasoline station follows Article 514. Its classified areas around dispensers come from Table 514.3(B)(1), unless the authority having jurisdiction determines that low-flash liquids such as gasoline will not be handled, in which case the location need not be classified (514.3(A)). Fuel dispensing systems must have one or more emergency shutoffs or electrical disconnects located not less than 20 ft nor more than 100 ft from the dispensers they serve (514.11(A)).

Health care facilities

Article 517 covers clinics, medical offices, and hospitals, and the technical rules depend on the category of the patient care space. Two points are worth knowing. Branch circuits to patient care spaces need an effective ground-fault path: a metal raceway or a metal-armored or sheathed cable that itself qualifies as an equipment grounding conductor, plus an insulated copper equipment grounding conductor identified by green insulation (517.13(A) and (B)). Type NM cable does not meet that. And in a Category 2 space, each patient bed location needs at least two branch circuits, one from the critical branch and one from the normal system, and a minimum of eight receptacles (517.18(A) and (B)(1)). The two-circuit rule does not apply to patient bed locations in clinics and medical or dental offices, so it is mainly a hospital rule. Anything more detailed is for the designer and the health care authority.

Assembly occupancies

Article 518 covers buildings, or portions of buildings, designed or intended for the gathering of 100 or more persons for worship, entertainment, eating, drinking, amusement, awaiting transportation, or similar purposes (518.1). The examples include assembly halls, auditoriums, gymnasiums, restaurants, conference rooms, multipurpose rooms, museums, and places of religious worship (518.2(A)). In a mixed building, Article 518 applies only to the assembly portion, and a room used for assembly by fewer than 100 persons and incidental to another occupancy is classified as part of that other occupancy (518.2(B)). That is why a church fellowship hall for 120 falls under it, while a conference room for 40 in an office does not.

The wiring method must qualify as an equipment grounding conductor or carry one, and the permitted methods are metal raceways, flexible metal raceways, nonmetallic raceways encased in at least 2 in. of concrete, and Type MI, MC, or AC cable (518.4(A)). NM cable, ENT, and rigid nonmetallic conduit are additionally permitted in buildings, or portions, that the building code does not require to be fire-rated construction (518.4(C)). Working spaces around outdoor equipment serving an assembly occupancy must be illuminated, and the lighting cannot be controlled by automatic means only (518.6).

Temporary installations: when and how long

Temporary wiring is a real installation with its own article, and the permanent-wiring rules still apply unless Article 590 modifies them (590.2(A)). Temporary wiring methods must also be approved for the conditions of use (590.2(B)). Time limits depend on the purpose. Temporary power and lighting is permitted during construction, remodeling, maintenance, repair, or demolition. It is permitted for not more than 90 days for holiday decorative lighting and similar purposes (590.3(B)), and that decorative lighting must be listed and labeled (590.5). It is also permitted for emergencies and tests (590.3(C)). Temporary wiring must be removed immediately when the construction or the purpose ends (590.3(D)).

Temporary wiring rules

Temporary services follow Article 230, and feeders and branch circuits are protected under 240.4 and 240.5 (590.4(A) to (C)). For temporary feeders and branch circuits, NM, NMC, and SE cable are allowed with no height limit and no building-construction-type limit, and without concealment in walls, floors, or ceilings. All receptacles are the grounding type, with an equipment grounding conductor to every one, and receptacles on construction sites may not be on a branch circuit that supplies temporary lighting (590.4(D)(1)). Fifteen and 20 ampere receptacles in wet locations use the in-use covers of 406.9(B)(1). Each temporary circuit needs a disconnect for all ungrounded conductors (590.4(E)). General-illumination lamps must be protected from contact and breakage by a luminaire or a lampholder with a guard, and a metal guard must be grounded (590.4(F)). Splices go in enclosures with covers, with limited construction-site exceptions (590.4(G)). Cords are protected at doorways and pinch points (590.4(H)). Feeder and branch-circuit cables and cords may not lie on the floor or ground, and vegetation may not support overhead spans (590.4(J)). Extension cords are exempt from that support rule.

GFCI protection on construction sites

Section 590.6 requires ground-fault protection for personnel on temporary wiring used to power equipment during construction, remodeling, maintenance, repair, or demolition. It applies to utility power and to power from on-site generators. The pathway depends on the receptacle.

Receptacle on the jobProtection required (590.6)
125 V, single-phase, 15, 20, or 30 A, not part of permanent wiring, in use by personnelGFCI for personnel (A)(1)
Same ratings, but installed or existing as permanent wiring and used for temporary powerGFCI for personnel (A)(2)
125 V and 125/250 V, 15, 20, or 30 A outlets on a portable generator of 15 kW or lessListed GFCI for personnel (A)(3)
Other receptacles, such as 250 V or 3-phaseGFCI, or a written assured equipment grounding conductor program (B)

An assured equipment grounding conductor program must be written and continuously enforced at the site by one or more designated persons who make sure the equipment grounding conductors of cord sets, temporary receptacles, and cord-and-plug equipment are installed and maintained. Temporary wiring over 600 volts needs fencing or barriers (590.7), and reused overcurrent devices must be examined for proper installation and signs of impending failure (590.8(A)).

Worked example: walking a job site

A GCHS project manager walks a new clinic build. The pedestal has 12 tool receptacles rated 125 V and 20 A. All 12 need GFCI protection for personnel, and they can share protection at the breaker or use receptacle-type GFCIs. Two 250 V, 50 A receptacles serve a hoist and a welder. Those two need GFCI, or the site must run a written assured equipment grounding conductor program. A 12 kW portable generator sits by the loading area, and every 125 V and 125/250 V outlet up to 30 A on it needs listed GFCI protection, because it is 15 kW or less. Eight bare lamps light the stair on a separate circuit: they need guards, and no receptacles may be added to that circuit. Four groups of equipment, four different rules. Extension cords lying in the doorway get flagged under 590.4(H).

Key numbers
  • Assembly occupancy: 100 or more persons (518.1)
  • Assembly wiring: metal methods; NM, ENT, RNC only in nonrated construction (518.4)
  • Fuel dispenser emergency shutoff: at least 20 ft and not more than 100 ft away (514.11(A))
  • Category 2 patient bed location: 2 circuits, 8 receptacles (517.18; circuit rule not for clinics)
  • Holiday decorative lighting: not over 90 days (590.3(B))
  • GFCI for personnel: 125 V, 15, 20, 30 A construction receptacles; generators 15 kW or less (590.6(A))
  • Receptacles not on a temporary lighting circuit (590.4(D)(1))

In the field

A GCHS rehab of a church annex includes a fellowship hall built for about 120. That puts the hall under Article 518, so the plan reviewer asks for the wiring method and the construction type, since NM cable is allowed in unrated construction only. During construction, the site walk is short and repeatable. Is every tool outlet GFCI protected, including the permanent receptacles the crew is borrowing? Are the lamps guarded and on their own circuit? Is anything laid on the floor or crossing a door? Is the generator's cord set or built-in protection listed for GFCI? The list takes five minutes, and it is the cheapest way to prevent shock injuries at a site.

Practice questions

1. A church building has a fellowship hall designed for 120 people, in the same building as classrooms and offices. Does Article 518 apply to the hall, and why?

  1. No, because Article 518 applies only to buildings used exclusively for assembly and not to a hall inside a larger building
  2. No, because Article 518 starts at 300 persons and the hall holds fewer than that number
  3. Yes, because that portion of the building is designed or intended for 100 or more persons
  4. Yes, but only if the hall has a stage or a projection booth for presentations

2. A GCHS community building has a 150-person assembly hall in unrated Type V-B construction. May the electrician run Type NM cable in the hall under Article 518?

  1. Yes, because NM cable is permitted in assembly portions that the building code does not require to be fire-rated construction
  2. No, because 518.4(A) allows only metal raceways, flexible metal raceways, and MC, MI, or AC cable in every assembly building
  3. No, because NM cable is prohibited in any building that holds 100 or more persons
  4. Yes, but only where the cable is installed exposed and covered by a metal guard

3. A grain-handling building has combustible grain dust in the air under normal operation in quantities that can form an ignitible mixture. How is the location classified under 500.5?

  1. Class I, Division 1, because grain dust is treated as a flammable vapor when it is airborne in a building
  2. Class III, Division 1, because grain is a fiber and flying material
  3. Class II, Division 2, because grain dust settles out of the air slowly
  4. Class II, Division 1, because combustible dust is present in the air under normal operating conditions

4. A Group S-2 open parking garage is used only to park passenger cars, with no repair or fueling. How does 511.3(A) treat its electrical classification?

  1. It must be Class I, Division 2 up to 18 in. above the floor throughout the garage
  2. It is permitted to be unclassified under 511.3(A)
  3. It must be Class I, Division 1 within 3 ft of every parked vehicle
  4. It must be Class II, Division 2 because of exhaust particles in the air

5. A Group B clinic exam room is a patient care space. The electrician wired its branch circuits with Type NM cable and no metal raceway. Does that meet 517.13(A)?

  1. Yes, because NM cable contains an equipment grounding conductor
  2. Yes, if the NM cable is enclosed in a nonmetallic raceway for protection
  3. No, because branch circuits to patient care spaces need a metal raceway or metal-armored or sheathed cable that itself qualifies as an equipment grounding conductor
  4. Yes, but only when the exam room is not a Category 2 space

6. A community center strings holiday decorative lighting on its front canopy as a temporary installation. How long may it stay up under 590.3(B)?

  1. Not more than 90 days
  2. Up to 180 days, with an extension by the authority having jurisdiction
  3. Not more than 30 days, the same as a special event permit
  4. For the full calendar year, if the lighting is listed

7. On a Group B construction site, an electrician connects eight 20 A receptacles to the same branch circuit that supplies the temporary lights. What does 590.4(D)(1) say?

  1. It is permitted if every receptacle on the circuit has GFCI protection and the lamps are guarded
  2. That is permitted if the circuit is 20 A and wired with 12 AWG copper
  3. That is permitted only during the first 90 days of the project
  4. Not permitted, because site receptacles may not share a circuit with temporary lighting

8. A crew hangs bare lamps for general illumination from cords in the stairwell of a building under construction. What does 590.4(F) require?

  1. Nothing, because temporary lighting is exempt from lamp protection
  2. The lamps must be protected from accidental contact or breakage by a luminaire or a lampholder with a guard, and a metal guard must be grounded
  3. The lamps must be mounted at least 12 ft above the floor
  4. The lamps must be low-voltage types supplied by a transformer

9. A temporary feeder cable is laid across the ground from the service pedestal to a panelboard in an addition that is being built. What is the finding under 590.4(J)?

  1. The cable is acceptable on the ground if it is a hard-usage or extra-hard-usage type cord
  2. The cable is acceptable on any project for up to 90 days
  3. Feeder cable may not lie on the ground; it must be supported off the ground
  4. The cable is acceptable if the feeder has GFCI protection

10. A hand drill on a new Group B construction site plugs into a 125 V, 20 A receptacle on a temporary pedestal that is not part of the building's permanent wiring. What protection does 590.6(A)(1) require?

  1. A written assured equipment grounding conductor program alone, with no GFCI
  2. GFCI protection for personnel
  3. Arc-fault circuit-interrupter protection in place of GFCI protection
  4. None, because the pedestal is not part of the building's wiring

11. During the rehab of a community center, workers plug tools into existing 125 V, 20 A receptacles that are part of the building's permanent wiring. Are those receptacles required to have GFCI protection for personnel?

  1. No, because GFCI protection applies only to outlets that are not part of the permanent wiring of the building
  2. No, if the circuits were inspected before the rehab started
  3. Yes, but only for receptacles that are located outdoors
  4. Yes, 590.6(A)(2) covers permanent-wiring receptacles used for temporary power

12. A 12 kW portable generator on a construction site has 125/250 V, 30 A outlets. What does 590.6(A)(3) require for those outlets?

  1. Listed GFCI protection for personnel, because the generator is 15 kW or smaller
  2. None, because a generator is not part of the building's wiring
  3. GFCI protection on the 125 V outlets only, since 125/250 V outlets are exempt from the rule
  4. GFCI protection only if the generator is larger than 15 kW

13. A 250 V, 3-phase, 50 A receptacle serves a welder on a Group B construction site. What does 590.6(B) require?

  1. Nothing, because 590.6 applies only to 125 V receptacles
  2. GFCI protection only, because the written program option is limited to dwelling construction sites
  3. GFCI protection for personnel, or a written assured equipment grounding conductor program
  4. A written program only, because GFCI devices are not made for 250 V circuits

14. A convenience store's gasoline dispensers have their emergency electrical disconnect mounted on a post 10 ft from the dispensers. What is the finding under 514.11(A)?

  1. It is acceptable, because the shutoff is required only within 50 ft of the dispensers
  2. It is too close; the minimum distance is 20 ft
  3. It is too far, because the shutoff must be within 5 ft so an attendant can reach it
  4. It is acceptable if the disconnect is located in the store's electrical room

Glossary

Class I location
A hazardous location where flammable gases or vapors are or may be present in ignitible quantities (500.5(B)).
Class II location
A hazardous location made hazardous by combustible dust (500.5(C)).
Division 1 and Division 2
Division 1 means the hazard exists under normal operation; Division 2 means it is normally confined and escapes only on failure or abnormal operation (500.5).
Assembly occupancy
A building or portion designed or intended for 100 or more persons to gather for worship, dining, entertainment, or similar purposes (518.1).
Temporary wiring
Wiring installed for construction, repair, holiday lighting, emergencies, or tests, and removed when its purpose ends (590.3(D)).
GFCI for personnel
Ground-fault circuit-interrupter protection that limits shock hazard, required on construction receptacles by 590.6.
Assured equipment grounding conductor program
A written program, continuously enforced by designated persons, that verifies the grounding conductors of cords and temporary receptacles (590.6(B)(2)).
Patient care space
An area of a health care facility where patients are examined or treated, classified by category and wired under Article 517.