Commercial Mechanical 100%

2021 IFGC Chapter 5 and IMC Chapter 8

Lesson 8: Chimneys and Vents

IFGC 503 · IMC 801 to 804 · 14 practice questions

0:00 / --:--

Reading

Burning fuel makes flue gas, and the code cares about two things: what carries it out, and where it ends up. This lesson follows 2021 IFGC Chapter 5 for gas appliances and then looks at IMC Chapter 8, which covers oil-fired and solid fuel appliances (IMC Section 801.1 sends gas appliances to the fuel gas code). The heart of the lesson is termination: how high a gravity vent must rise, and how far a through-the-wall terminal must stay from windows, grade, air inlets and neighbors. Lesson 1 explains why you confirm which mechanical and fuel gas editions your city has adopted before you quote any of these numbers.

Vent termination clearances for a roof gas vent and through-the-wall terminals Left, a section: a Type B vent rises from a boiler draft hood 8 feet above the floor through a roof at 12 feet, beside a taller building part at 15 feet that is 7 feet away. The vent top must be 5 feet above the hood (13 feet), 2 feet above the roof (14 feet) and 2 feet above the taller part (17 feet), so 17 feet governs. Right, a wall elevation: a terminal is 12 inches above grade, a direct-vent terminal is 12 inches from an openable window, and a nondirect-vent terminal is 4 feet to the side of the window. Roof gas vent, Type B, natural draft Through-the-wall terminals, front view Roof 12 ft Boiler 5 ft 2 ft 2 ft Top at 17 ft Taller part 15 ft high, 7 ft away Floor Vent top must clear all three (503.6) Draft hood at 8 ft: 8 + 5 = 13 ft Roof at 12 ft: 12 + 2 = 14 ft Taller part within 10 ft: 15 + 2 = 17 ft The highest governs: at least 17 ft Connector rises 1/4 in per ft, no dips or sags. Finished grade Openable window Direct-vent, 120,000 Btu/h Nondirect-vent 12 in 4 ft 12 in above grade Table 503.8 highlights Direct-vent to openable window or door: 6 in to 10,000 Btu/h, 9 in to 50,000, 12 in to 150,000, above that per maker Nondirect-vent: 4 ft below or beside, 1 ft above Mechanical air inlet: 10 ft away or 3 ft above Regulator vent: 3 ft (to 2 psi), 10 ft (over 2 psi) Public sidewalk or driveway: 7 ft above Under a porch: 12 in, only if open on two sides
Left: three height checks on one gas vent. Right: the same wall, a terminal near grade, and two terminals near one window.

Choosing the vent (Table 503.4)

Every appliance must connect to a venting system unless a listed exception applies, such as a listed direct-vent unit (503.2). Table 503.4 matches vent to appliance. A listed Category I appliance, or one with a draft hood, may use a Type B gas vent, a chimney, single-wall metal pipe, a listed chimney lining system or a listed special gas vent. Vented wall furnaces use Type B-W vent. Category II, III and IV appliances use whatever the manufacturer specifies or furnishes. A listed combination gas and oil appliance may use Type L vent or a chimney, and unlisted appliances, appliances that could be converted to solid fuel, and appliances listed for chimney use only need a chimney. The category numbers come from the appliance listing, so read the data plate rather than guessing. Where plastic pipe is used, the appliance must be listed for it, the instructions must name the material, the pipe must carry the required label, and any primer must be a contrasting color (503.4.1, 503.4.1.1). Category II and IV appliances and other condensing appliances must have condensate collected and drained (503.9).

Chimneys and gas vent terminations (503.5.4, 503.6)

A chimney serving a residential-type or low-heat appliance rises at least 3 feet above where it passes through the roof and at least 2 feet higher than any part of the building within 10 feet horizontally. A chimney for a medium-heat appliance rises at least 10 feet higher than any building portion within 25 feet, and every chimney rises at least 5 feet above the highest draft hood outlet or flue collar connected to it (503.5.4). A gas vent has three tests (503.6). A vent 12 inches or less in size and at least 8 feet from a vertical wall ends above the roof as Figure 503.6.5 shows. A larger vent, or one closer than 8 feet to a wall or similar obstruction, ends at least 2 feet above the highest point where it passes through the roof and at least 2 feet above any part of a building within 10 feet horizontally. A Type B or L vent also ends at least 5 feet above the highest connected draft hood or flue collar, and a Type B-W vent at least 12 feet above the bottom of the wall furnace (503.6.6). The vent goes through roof flashing and finishes with a listed cap (503.6.7), and it stays at least 3 feet above any forced-air inlet within 10 feet (503.6.8).

Worked example. A boiler draft hood sits 8 feet above the floor of a one-story community building, and the vent passes through a roof 12 feet above the floor. A taller part of the building rises to 15 feet, 7 feet from the vent. Because that wall is closer than 8 feet, the 2 foot tests of 503.6.5 apply, along with the 5 foot draft hood test of 503.6.6. The height tests are: hood, 8 + 5 = 13 feet; roof, 12 + 2 = 14 feet; taller part within 10 feet, 15 + 2 = 17 feet. The vent must reach at least 17 feet.

Vent connectors (503.10)

A connector joins the appliance to the vent unless the vent attaches directly (503.10.1). It slopes up toward the vent at least 1/4 inch per foot with no dips or sags (503.10.8). The maximum horizontal length of a single-wall connector is 75 percent of the vent or chimney height, and of a Type B double-wall connector 100 percent (503.10.9). Joined connectors use a tee or wye (503.10.7), the connector may not attach to a fireplace flue unless that flue opening is permanently sealed (503.10.13), and its whole length needs ready access for inspection, cleaning and replacement (503.10.12). Clearance to combustibles comes from Table 503.10.5: for residential and low-heat appliances not otherwise listed, single-wall connector needs 18 inches, Type L needs 9 inches, and Type B is not permitted; for medium-heat appliances, single-wall needs 36 inches; and the listing controls where it says something different. Connector example: on a 20 foot vent, a single-wall connector can run 15 feet horizontally and a Type B connector 20 feet. A 12 foot connector must climb at least 12 x 1/4 = 3 inches.

Through-the-wall terminals (503.8)

Direct-vent appliances and appliances with integral vents end at a sidewall terminal, and Table 503.8 sets the clearances. It does not apply to the combustion air intake of a direct-vent appliance. The table gives one column for direct-vent terminals and one for nondirect-vent terminals; rows with a single entry apply to both.

Clearance from the terminal toMinimum (Table 503.8)
Finished grade, veranda, porch, deck or balcony12 in
Openable window or door, direct-vent6 in to 10,000 Btu/h; 9 in to 50,000; 12 in to 150,000; above 150,000 per the maker and no less than the nondirect-vent clearance
Openable window or door, nondirect-vent4 ft below or beside; 1 ft above
Mechanical air supply inlet10 ft horizontally, or 3 ft above the inlet
Service regulator vent outlet3 ft up to 2 psi gas; 10 ft above 2 psi
Paved sidewalk or driveway on public property7 ft above, and not over public walkways where condensate or vapor is a nuisance
Underside of porch, deck or balcony12 in if open on at least two sides; prohibited if open on only one

Fixed windows, soffits and building corners carry no table clearance unless the maker requires one, and a nonmechanical air inlet or another appliance's combustion air inlet follows the window row. Example: a 120,000 Btu/h direct-vent boiler needs 12 inches to an openable window, while a 45,000 Btu/h unit needs 9 inches. A nondirect-vent unit needs 4 feet from the same window unless it ends 1 foot above it.

Mechanical draft and other protections (503.3, 503.15, 503.16)

Mechanical draft systems, forced or induced, must be listed to UL 378 and installed to the maker's instructions. Parts under positive pressure must not leak flue gas into the building, a natural-draft appliance may not connect to a positive-pressure part, and gas flow to the burner must stop when the draft system is not performing (503.3.3). A vent may not pass through a fabricated air duct or furnace plenum (503.3.5). Through an above-ceiling air-handling space it needs a listed special or positive-pressure vent with sealed joints, no joints in the space, or a sealed enclosure (503.3.6). Nothing that slows flue flow may be added to a connector, chimney or vent, apart from listed regulators, vent dampers and heat reclaimers (503.15). The annular space where any vent, including direct-vent, passes through an outside wall must be permanently sealed (503.16). A gas vent through an exterior wall does not end adjacent to the wall or below eaves or parapets, except direct-vent and mechanical draft systems (503.6.9).

IMC Chapter 8: oil-fired and solid fuel appliances

Where the IMC governs, vents are listed and labeled (802.1), and a Type L vent ends with a listed cap at least 2 feet above the roof penetration and 2 feet above anything within 10 feet (802.4, 802.5). Vents rise 5 feet above the highest flue collar unless an exception applies (802.6). Connectors pitch at least 1/4 unit in 12 (803.10.5). Power exhausters end at least 10 feet from the lot line or adjacent buildings (804.3.3). Horizontal mechanical draft terminals stay at least 7 feet over a walkway, 3 feet above a forced-air inlet within 10 feet, and 4 feet below, 4 feet to the side or 1 foot above any door, window or gravity air inlet. They also stay at least 3 feet from an inside corner, 12 inches above grade, and out from above or within 3 feet of an oil tank vent or gas meter (804.3.4). Natural-draft integral vent terminals are 9 inches apart and forced-draft ones 12 inches apart (804.2.1).

In the field

A crew swaps an old gravity-vented boiler in a church annex for a sealed-combustion sidewall unit and drills the terminal under a covered entry that is open on one side only. That location is prohibited by Table 503.8, no matter the size of the appliance, because vapor collects under the cover. Also check the height: shrubs, mulch and new landscape beds have a way of raising finished grade, which eats into the 12 inch clearance. Measure from the finished grade, and look at what stands within 4 feet of the terminal.

Key numbers
  • Gas vent: 2 ft above the roof passage and above anything within 10 ft; 5 ft above the draft hood (503.6)
  • Chimney, residential or low-heat: 3 ft above the roof and 2 ft above anything within 10 ft (503.5.4)
  • Connector slope 1/4 in per ft; length 75 percent (single-wall) or 100 percent (Type B) of vent height (503.10)
  • Terminal to grade 12 in; to openable window 6, 9 or 12 in by input for direct-vent (Table 503.8)
  • Nondirect-vent to window: 4 ft below or beside, 1 ft above (Table 503.8)

Practice questions

1. A Type B gas vent serves a boiler in a Group R-2 apartment building. The vent is 6 feet from the wall of a taller part of the building. Under IFGC 503.6.5, how must it end relative to that taller part?

  1. At least 5 feet from the wall, regardless of its height
  2. Level with the top of the taller wall
  3. At least 10 feet above the top of the wall
  4. At least 2 feet above any building portion within 10 feet

2. The draft hood of a boiler in a Group B clinic is 9 feet above the floor. The vent passes through a roof at 11 feet, and a taller roof at 15 feet is 6 feet away. What is the least height above the floor for the vent top?

  1. 14 feet
  2. 17 feet
  3. 13 feet
  4. 20 feet

3. A Type B-W gas vent serves a vented wall furnace in a Group R-2 rehab unit. Under IFGC 503.6.6, it must end at least how far above the bottom of the wall furnace?

  1. 12 feet
  2. 5 feet
  3. 2 feet
  4. 3 feet

4. A masonry chimney serves a residential-type gas appliance in a Group R-3 building. The chimney passes through the roof at 12 feet, and a taller portion of the building 8 feet away is 20 feet high. Under IFGC 503.5.4, what is the minimum chimney top height?

  1. 15 feet
  2. 20 feet
  3. 14 feet
  4. 22 feet

5. A chimney serves a medium-heat appliance in a Group F-1 plant. A building portion within 25 feet has a roof at 30 feet. Under IFGC 503.5.4, the chimney top must be at least:

  1. 32 feet
  2. 33 feet
  3. 40 feet
  4. 35 feet

6. A gas vent connector in a Group B office runs 12 feet horizontally to the vent. Under IFGC 503.10.8, what is the least rise it must have along its length?

  1. 1 inch
  2. 6 inches
  3. 12 inches
  4. 3 inches

7. A 24-foot-tall vent serves a low-heat appliance in a Group S-1 warehouse and uses a single-wall connector. Under IFGC 503.10.9, the maximum horizontal length of the connector is:

  1. 24 feet
  2. 18 feet
  3. 12 feet
  4. 6 feet

8. A direct-vent boiler terminal is being set on the wall of a Group A-3 community hall next to a landscaped bed. Under IFGC Table 503.8, the terminal must be at least how far above finished grade?

  1. 6 inches
  2. 3 feet
  3. 12 inches
  4. 18 inches

9. A 45,000 Btu/h direct-vent unit heater is being set on the wall of a Group B office. The nearest openable window is on the same wall. Under IFGC Table 503.8, the minimum clearance from the terminal to the window is:

  1. 9 inches
  2. 6 inches
  3. 12 inches
  4. 4 feet

10. A nondirect-vent terminal on a wall in a Group R-2 building is at the same level as an openable window. Under IFGC Table 503.8, how far must it be to the side of the window?

  1. 4 feet
  2. 1 foot
  3. 9 inches
  4. 10 feet

11. A contractor mounts a sidewall vent terminal under a covered porch of a Group R-2 building. The porch is open on only one side. Under IFGC Table 503.8, this location is:

  1. Allowed with 12 inches of clearance to the underside
  2. Allowed if the terminal is a direct-vent type
  3. Prohibited, since it is open on only one side
  4. Allowed with 3 feet of clearance to the underside

12. A mechanical draft system serves a gas boiler in a Group B building. Under IFGC 503.3.3, which statement is correct?

  1. Any mechanical draft fan may be used if it is quiet enough for the space
  2. A natural-draft appliance may not connect to a positive-pressure part
  3. The burner may keep running when the fan has failed, if the flue is warm
  4. Positive-pressure joints need not be gastight if they are accessible

13. An oil-fired boiler with a power exhauster is installed in a Group B building under the IMC. Under IMC 804.3.3, the vent termination must be at least how far from the lot line and adjacent buildings?

  1. 3 feet
  2. 5 feet
  3. 7 feet
  4. 10 feet

14. A crew installs a direct-vent water heater in a Group R-2 rehab and leaves a gap around the vent pipe where it passes through the outside wall. Under IFGC 503.16, the annular space must be:

  1. Left open so combustion air can enter the wall
  2. Permanently sealed with approved materials
  3. Filled with loose fiberglass insulation
  4. Covered with a screen of wire mesh

Glossary

Gas vent
A listed, factory-built vent (such as Type B) for natural-draft appliances, running from the draft hood or flue collar to the outdoors.
Chimney
A masonry, metal or factory-built flue for appliances that need more than a gas vent, such as those listed for chimney use only.
Vent connector
The pipe that joins an appliance flue collar or draft hood to the vent or chimney.
Direct-vent appliance
An appliance with a sealed combustion system that takes all its air from outdoors and sends all flue gases directly outdoors.
Nondirect-vent terminal
A sidewall termination for an appliance that draws combustion air from the room, so it needs larger clearances.
Mechanical draft
Venting driven by a fan, either forcing flue gases out or drawing them out.
Category I appliance
A listed appliance that vents by natural draft and normally uses a Type B gas vent or a chimney.
Type B-W vent
A gas vent listed for use with vented wall furnaces.