2021 IRC Chapter 5

Lesson 6: Floor Framing: Spans, Bearing, Notching, and Draftstopping

IRC R502 · 14 practice questions

0:00 / --:--

Reading

A floor framing inspection mostly asks whether the lumber that went into the floor is what the plans and span tables assumed, and whether anyone has cut it up afterward in ways the code does not allow. Add how the joists bear and connect at openings and supports, and whether the floor cavity needs dividing against fire spread, and you have covered nearly everything a GCHS inspector checks at a floor framing visit, whether it is new infill construction or a rehab job where the crew opened up an existing floor. Every number below carries its IRC section so it can be checked against the edition your jurisdiction has adopted.

Lumber grading and span tables

Joists, girders, and other structural floor lumber must carry a grade mark, or an accompanying certificate of inspection, from an accredited grading or inspection agency (IRC R502.1.1). That stamp ties a specific piece of wood to the allowable-span tables the design relied on: species, grade, size, spacing, and design load all feed into the allowed span, and an inspector mainly confirms the framing on site matches what the approved plans and table allow. One distinction matters: the code publishes separate span tables for sleeping rooms and other habitable spaces, since a bedroom is designed for 30 psf live load while other habitable rooms use 40 psf (Table R301.5): Table R502.3.1(1) covers sleeping areas at 30 psf and Table R502.3.1(2) covers other areas at 40 psf (R502.3.1, R502.3.2). Using the lighter table for a room that could later be furnished as a living area over-spans the joists, so when a room's use is uncertain, the heavier table is the safe read.

Bearing at supports

Joist and girder ends need a minimum bearing length wherever they land directly on a support: 1-1/2 inches on wood or metal, 3 inches on masonry or concrete (IRC R502.6), or an approved hanger installed with the exact fasteners the manufacturer specifies as the alternative. Masonry takes more bearing length because it is weaker in localized crushing than steel or wood. Where joists frame from opposite sides of a beam and lap over the support instead of running continuously, R502.6.1 requires a minimum 3-inch lap, face-nailed together with at least three 10d nails, or an equivalent wood or metal splice, giving the two joists a continuous tension tie across the support rather than added bearing area. Joists framing into the side of a wood girder must be carried by approved framing anchors or by ledger strips not less than nominal 2x2 (R502.6.2).

Lateral restraint, blocking, and bridging

Joist ends need lateral restraint so a joist cannot rotate off its bearing under load (IRC R502.7). Full-depth solid blocking, a continuous rim (band) joist, a full-depth header, or attachment to an adjoining stud all satisfy that; a single toenail does not, since it resists almost no twisting. Deep, narrow joists also want to roll over sideways along their length, not just at the ends. Where solid-sawn joists exceed a nominal 2x12, R502.7.1 requires intermediate lateral support, solid blocking, diagonal bridging, or a continuous 1x3 strip across the bottom of the joists, at intervals not exceeding 8 feet. Neither blocking nor bridging adds span capacity; both exist to hold slender members upright and share concentrated loads between neighboring joists.

Notching and boring sawn lumber

Cutting into a joist for plumbing, wiring, or ductwork is where floor framing inspections most often find a defect, and IRC R502.8 sets firm limits for sawn lumber. A notch in the top or bottom edge is limited to one-sixth of the joist depth, may not be longer than one-third of the depth, and is prohibited outright in the middle third of the span, where bending stress peaks. An end notch can go deeper, up to one-fourth the depth, since a simple span's end carries shear rather than peak bending stress. A bored hole cannot exceed one-third of the depth in diameter, and must stay at least 2 inches clear of the top and bottom edges and of any other hole or notch, since the material between close holes is too thin to transfer load around them.

Cut in a sawn joist (D = actual joist depth)Limit
Notch, top or bottom edgeMax D/6 deep and D/3 long; never in the middle third of the span
Notch at the end of the joistMax D/4
Bored hole diameterMax D/3
Hole edge distanceAt least 2 in. from top and bottom edges, and 2 in. from any other hole or notch
Key numbers
  • Bearing: 1-1/2 in. on wood or metal, 3 in. on masonry or concrete (R502.6)
  • Lapped joists: 3 in. minimum lap, three 10d face nails minimum (R502.6.1)
  • Ledger strip minimum size: nominal 2x2 (R502.6.2)
  • Deep-joist blocking/bridging (over nominal 2x12): intervals not exceeding 8 ft (R502.7.1)
  • Notch/hole limits: edge notch D/6, end notch D/4, bored hole D/3, 2 in. edge clearance (R502.8)
  • Header framing an opening: single member the same size as the joists at 4 ft or less; header and trimmers doubled past 4 ft (R502.10)
  • Subfloor panel nailing (19/32 to 3/4 in. panels): 6 in. on center at panel edges, 12 in. at intermediate supports (Table R602.3(1))
  • Draftstopping: where usable space is above and below, limit the concealed floor-ceiling space to 1,000 sq ft (R302.12)

Engineered lumber plays by different rules

The D/6, D/4, and D/3 rules apply to sawn lumber only. I-joists, LVL, and floor trusses may be cut, notched, or drilled only where the manufacturer's recommendations allow it, or a registered design professional has designed for the cut (R502.8.2). An I-joist's flanges carry essentially all its bending capacity, so flange cuts are prohibited, and web holes are permitted only in the manufacturer's hole zones, tighter near a bearing point where shear peaks. Web stiffeners keep the thin web from buckling under a concentrated load. Squash blocks, cut slightly taller than the joist and set alongside it under a post or wall above, carry that point load in direct bearing to the support, bypassing the flange's weak crushing capacity. A field-cut truss chord notch is a red flag regardless of size: truss members may not be cut, notched, spliced, or otherwise altered without a registered design professional's approval (R502.11.3), and the truss design drawings, not a span table, govern bearing points and bracing.

In the field

A common rehab find: a plumber has notched the top edge of an existing 2x10 joist near mid-span for a drain line, and the cut looks shallow enough to seem harmless. Depth is only half the check; even a shallow notch is prohibited outright in the middle third of the span, where the joist is doing the most work resisting bending. The fix is almost never "leave it," it is a sistered joist, an engineered repair bracket, or rerouting the line through an adjacent bay's web, not a judgment call about how deep the cut looks.

Framing floor openings for stairs, chimneys, and chases

Where a floor opening for a stairway or chimney chase needs a header joist to carry the ends of interrupted joists, R502.10 keys everything to the header span. At 4 feet or less, the header can be a single member the same size as the floor joists, and a single trimmer can carry a single header located within 3 feet of the trimmer bearing. Past a 4-foot header span, both the header and the trimmer joists must be doubled and sized to support the joists framing into the header, since the trimmers now pick up the tail joists' reactions on top of their own load.

Worked example. Bore a 3-inch hole through a 2x10 joist, actual depth 9-1/4 inches. Diameter limit D/3 = 9.25 ÷ 3 = 3.08 inches, so 3 inches passes. Centered on the depth, that hole leaves (9.25 − 3) ÷ 2 = 3.1 inches clear each side, past the 2-inch minimum. The same hole pushed low, leaving only 1-1/2 inches below it, fails edge distance even though the diameter is fine, exactly the hole an inspector rejects on site.

Subfloor sheathing

Wood structural panel subflooring is installed with its long dimension (the strength axis) perpendicular to the joists, since the span tables assume panels run continuously over two or more spans in that direction (Table R503.2.1.1(1)). Panels are attached to wood framing per Table R602.3(1) (R503.2.3). For 19/32 to 3/4 inch panels with 8d common nails, that schedule calls for fasteners 6 inches on center at panel edges and 12 inches at intermediate supports, tighter at the edges where a panel wants to lift. Unsupported panel edges must have tongue-and-groove joints or blocking, unless an underlayment or finish flooring alternative listed in the table footnotes is used; an unsupported butt edge deflects independently under foot traffic and shows up later as a ridge or a cracked tile line.

Draftstopping

In combustible construction, where a floor-ceiling assembly has usable space both above and below its concealed space, draftstops must be installed so the concealed area does not exceed 1,000 square feet, dividing it into approximately equal areas (IRC R302.12). Where the assembly is enclosed by a floor membrane above and a ceiling membrane below, the code names two circumstances that call for draftstopping: a ceiling suspended under the floor framing, and floor framing of truss-type open-web or perforated members. Acceptable material is not less than 1/2-inch gypsum board or 3/8-inch wood structural panel, or other approved material, adequately supported, and it is installed parallel to the floor framing members unless the building official approves otherwise (R302.12.1). An ordinary solid-sawn joist bay with drywall fastened directly to the underside is already compartmented bay by bay and is not one of those two circumstances, while a dropped ceiling or open-web trusses open up one large continuous space, exactly the condition the rule targets.

Notching and boring limits for a sawn floor joist Section through a floor joist showing the middle third of the span where no edge notch is permitted, an edge notch limited to one-sixth of the joist depth outside that zone, an end notch limited to one-fourth of the depth, and a bored hole limited to one-third of the depth with 2 inches of clearance from the top and bottom edges and from any other hole or notch. Middle third of span: no edge notch permitted Edge notch Max D/6 End notch Max D/4 Bored hole Max D/3 2 in. min to edge 2 in. min to edge Full joist span Middle third (no edge notch anywhere in this zone)
A joist's location on the span, not just the size of the cut, decides whether a notch is legal: the same shallow edge notch that is fine near a support is prohibited outright in the middle third.
Separate the three solid-joist checksA solid joist is divided into thirds. The middle third is marked as a no-edge-notch zone, and callouts distinguish an edge notch, an end notch, and a bored hole. Refer to the existing dimensioned diagram for all limits. Middle third: no edge notchEnd notchCheck the end-notch limitEdge notchCheck depth and locationBored holeCheck diameter and edge clearanceUse the dimensioned figure for the full set of limits.Solid sawn joist, schematic only.
Treat notch type, location, hole diameter, and remaining wood at the edges as separate checks. This overview accompanies the original dimensioned figure and does not replace its limits.

Practice questions

1. What minimum bearing length does IRC R502.6 require for a floor joist end on a masonry foundation wall?

  1. 1-1/2 inches
  2. 2 inches
  3. 3 inches
  4. 6 inches

2. Joists lapped over a girder instead of running continuously must, per R502.6.1:

  1. Overlap at least 3 inches, held together by construction adhesive instead of nails
  2. Be cut flush and butted over the girder, tied with a single metal strap on one face
  3. Overlap at least 12 inches and be fastened with construction adhesive and one 8d nail
  4. Overlap at least 3 inches and be face-nailed with at least three 10d nails, or use an equivalent splice

3. Which of these satisfies the lateral restraint requirement at a floor joist end under R502.7?

  1. A single toenail into the plate
  2. Resting the joist on the plate with no other connection
  3. A finish nail into the subfloor above
  4. A continuous rim (band) joist

4. Solid-sawn joists deeper than a nominal 2x12 need intermediate blocking or bridging at intervals not exceeding:

  1. 8 feet
  2. 4 feet
  3. 12 feet
  4. 16 feet

5. A notch is cut into the top edge of a sawn floor joist at the exact center of its span. Per R502.8, this notch is:

  1. Allowed if it is less than D/6 deep, since that limit applies anywhere on the span
  2. Never allowed, at any depth, because the middle third is off limits to edge notches
  3. Allowed if it is patched afterward with a wood block glued into the notch
  4. Allowed up to D/4, the same limit that applies at the ends, if it is on the top edge

6. Why is an end notch in a sawn joist allowed to be deeper (D/4) than an edge notch elsewhere on the span (D/6)?

  1. The end of the joist is cut from a denser species than the rest of the member
  2. End notches are cosmetic only and are not counted in the code's structural limits
  3. Near a simple support the joist sees mostly shear, not peak bending stress
  4. There is no real difference; D/4 and D/6 apply to the same locations on the span

7. The maximum diameter of a bored hole in a sawn floor joist, per R502.8, is:

  1. One-third the joist depth (D/3)
  2. One-sixth the joist depth (D/6)
  3. One-half the joist depth
  4. 4 inches regardless of joist size

8. A 2x10 joist has an actual depth of 9-1/4 inches. The largest bored hole diameter permitted is approximately:

  1. 1-1/2 inches
  2. 2-5/16 inches
  3. 4-5/8 inches
  4. 3 inches

9. Which practice is acceptable on a factory-built floor truss without an engineered repair?

  1. Notching the bottom chord for a drain line, if the notch is under one-sixth of the chord depth
  2. Cutting a top chord to level a subfloor, if a sistered 2x4 is added afterward
  3. Running ductwork or wiring through the open web space between chords
  4. Trimming a web member to clear a duct, once the truss supplier has been told about it

10. An I-joist needs a hole drilled through its web for a supply line directly over an interior bearing wall. The correct guidance is:

  1. Apply the sawn-lumber D/3 rule, keeping the hole at least 2 inches from the flanges
  2. Follow the manufacturer's hole chart, most restrictive right at a bearing
  3. Drill anywhere in the web as long as the flange is untouched and the hole is under one-third of the web depth
  4. Holes are never allowed in an I-joist web under any circumstances or manufacturer instructions

11. A floor opening has a header joist spanning 5 feet. Per R502.10, the header and trimmer joists must be:

  1. Both doubled, since the header span exceeds 4 feet and the trimmers pick up the tail joists' reactions
  2. Single members the same size as the floor joists, since doubling starts past 8 feet
  3. Only the header doubled, with single trimmers, since trimmers never need to be doubled
  4. Single members, with a metal strap across the opening in place of doubling

12. A header joist framing a floor opening spans 3 feet. Per R502.10, the header may be:

  1. Doubled, with the trimmers also doubled, since every header needs two members
  2. A single member the same size as the floor joists
  3. A single member one size deeper than the floor joists, since it carries tail joists
  4. Doubled, with approved hangers required at both ends of the header

13. For a 3/4-inch wood structural panel subfloor on wood joists, Table R602.3(1) calls for fasteners spaced at:

  1. 12 inches on center at the panel edges and at every intermediate support
  2. 4 inches on center at the panel edges and 4 inches on center in the field
  3. 6 inches on center at panel edges and 12 inches at intermediate supports
  4. 6 inches on center in the field only, with no fasteners along panel edges

14. Draftstopping is required in a floor-ceiling assembly, per R302.12, when:

  1. The dwelling has more than one story, since each floor-ceiling assembly must be subdivided
  2. It has usable space above and below, and a suspended ceiling or open-web framing leaves over 1,000 square feet concealed
  3. Any recessed light fixtures are installed in the ceiling below the floor framing
  4. The floor uses solid-sawn joists of any depth, since deep joists create larger concealed voids

Glossary

Bearing
The contact length between a joist or girder end and its support; 1-1/2 inches minimum on wood or metal, 3 inches on masonry or concrete.
Lateral restraint
Support that keeps a joist end from rotating off its bearing, provided by blocking, a rim joist, a header, or an adjoining stud.
Trimmer joist
A joist running alongside a floor opening that carries the header joist framing that opening.
Squash block
A block set beside an I-joist under a post or bearing wall to carry the point load in direct bearing, bypassing the I-joist flange.
Web stiffener
A reinforcing block applied to an I-joist web at a concentrated load or bearing point to keep the thin web from buckling.
Draftstopping
A fire-resistant barrier dividing a large concealed space in a floor-ceiling assembly into smaller compartments, so no area exceeds 1,000 square feet where there is usable space above and below.
Ledger strip
A nominal 2x2 minimum strip fastened to the side of a wood girder to support joist ends where framing anchors are not used.
Span table
The code table giving allowable joist spans by species, grade, size, spacing, and design load; requires a valid grade stamp to apply.