This lesson covers two things that look unrelated but both come up constantly in GCHS rehab and infill work: concrete floors on grade, and wood decks. Slabs are a materials-and-moisture check. Decks are a load path check, from the ledger bolted to the house all the way down to the footing, and a deck built by an unpermitted handyman crew is one of the most common life-safety problems GCHS inspectors find on an older property. The deck material below restates the 2021 IRC's prescriptive deck provisions (IRC R507) together with the American Wood Council's DCA 6 prescriptive deck guide, which is written to walk through the same provisions with worked tables and details.

Concrete slab thickness and base

A concrete slab-on-ground floor must be at least 3-1/2 inches thick (IRC R506.1), placed on a subgrade that has had vegetation and organic material removed, since decomposing organic matter under a slab leaves voids that lead to cracking and settlement. Where the slab is placed below grade, R506.2.2 adds a 4-inch base course of clean graded sand, gravel, crushed stone, or similar material passing a 2-inch sieve, to provide uniform support and a capillary break. That base course can be omitted where the slab sits on well-drained Group I sand-gravel soils under the Unified Soil Classification System, since those soils already drain freely on their own.

Vapor retarder

Unless the slab falls under an exception, R506.2.3 requires a vapor retarder of at least 10 mil conforming to ASTM E1745 Class A, with joints lapped not less than 6 inches, placed between the concrete and the base course, or the prepared subgrade where there is no base course. Placement matters: the retarder has to sit immediately under the slab, not below the gravel, or the gravel stays free to hold and transmit ground moisture straight into the concrete above it. The exceptions are garages, utility buildings, and other unheated accessory structures; unheated storage rooms under 70 square feet and carports; driveways, walks, patios, and other flatwork not likely to be enclosed and heated later; and cases where the building official approves it based on local site conditions. None of those spaces put ground moisture in contact with a finished, occupied interior.

Deck scope and live load

IRC R507 covers wood-framed decks built with the prescriptive joist, beam, post, and footing sizing the section provides. R507.1 has decks designed for the live load in Table R301.5, which is 40 pounds per square foot for decks, or for the ground snow load in Table R301.2, whichever is greater. The 40 psf figure matches habitable rooms other than sleeping rooms, on the assumption that a deck sees furniture, gatherings, and occasional crowding rather than a lighter, bedroom-only load. Once a deck's loading, span, or configuration falls outside what the prescriptive tables cover, R507.1 sends the design to Section R301, which is exactly the gap DCA 6 exists to help a builder or inspector recognize before it becomes a problem discovered after the deck is already up.

The ledger connection

A deck ledger must be a minimum nominal 2x8 of pressure-preservative-treated Southern pine, incised pressure-preservative-treated hem-fir, or approved, naturally durable No. 2 grade or better lumber, and it may not support concentrated loads from beams or girders (R507.9.1.1). The band joist it attaches to must bear fully on the primary structure (R507.9.1.2). Ledger fasteners are 1/2-inch lag screws or 1/2-inch bolts, hot-dipped galvanized or stainless steel, spaced per Table R507.9.1.3(1) by joist span, load, fastener type, and sheathing thickness (R507.9.1.3); the lag screw tip must fully extend past the inside face of the band joist. Fasteners and connectors within 300 feet of a salt water shoreline must be stainless steel (Table R507.2.3), which matters along the Gulf Coast. A deck ledger may not be supported on stone or masonry veneer, so the veneer has to be removed down to the framing, or the deck has to be supported another way, such as a freestanding deck. Where decks have cantilevered framing, R507.8 requires the connection to resist uplift from the full live load on the cantilevered portion, and where a positive connection to the house cannot be verified at inspection, the deck must be self-supporting. Flashing is required at the ledger to keep water from reaching the house band joist (R507.2.4 and Table R507.9.1.3(1) note b); it is corrosion-resistant metal not less than 0.019 inch thick or approved nonmetallic material, since a ledger is one of the most common places a house frame rots from the outside in.

Lateral load connection

A deck that only leans on its ledger bolts for lateral support can pull away from the house under a lateral load, a mechanism serious enough that several deck collapses have been traced to it. R507.9.2 requires lateral loads to be transferred to the ground or to a structure that can carry them there. Where the connection follows Figure R507.9.2(1), that means hold-down tension devices in at least two locations per deck, within 24 inches of each end of the deck, each with an allowable capacity of at least 1,500 pounds. Where it follows Figure R507.9.2(2), it means at least four devices at 750 pounds each. Typical details, drawn in the figures, tie a deck joist through the house rim joist into a house floor joist. This is a connection an inspector has to trace through the framing, not just look for on the exterior face, since the visible hardware on the deck side is only half of it.

Posts, beams, and footings

Deck footings are sized from the tributary area and soil bearing value in Table R507.3.1. They must be placed at least 12 inches below the undisturbed ground surface (R507.3.2), and where the deck is attached to a frost-protected structure they must also extend below the frost line, bear on solid rock, or be protected another approved way (R507.3.3). R507.4 sizes single-level deck posts from Table R507.4 by species, post size, load, and tributary area, with height measured from the underside of the beam to the top of the footing. At 40 psf live load, a Douglas fir, hem-fir, or spruce-pine-fir 4x4 is limited to 8 feet at 100 square feet of tributary area, 7 feet at 120, and 5 feet 3 inches at 160, so a 4x4 gets shorter as the area grows; a 4x6 or larger allows more height. Beam ends need at least 1-1/2 inches of bearing on wood or metal and 3 inches on concrete or masonry, and each ply of a beam over an intermediate post needs full bearing on the post (R507.5.1). Notched post-to-beam connections follow Figure R507.5.1(2), whose dimensions are in the drawing and are not restated here, and the beam still needs a positive connection, bolts with washers or a manufactured connector sized for the post and beam, not a toenail (R507.5.2). Many builders and inspectors prefer an unnotched post with a cap or saddle connector instead. A 4x4 post that supports guard loads at the top of a guard may not be notched at the connection to the supporting structure (R507.10.2). Beam spans come from Tables R507.5(1) through R507.5(4) by species, size, and effective joist span (DCA 6 restates these tables in an easier lookup format).

Deck joists and guards

Deck joists bearing on top of a single-ply beam or ledger must be attached by a mechanical connector; joists framing into the side of a beam or ledger must be supported by approved joist hangers; and joists on a multiple-ply beam or ledger are fastened per Table R602.3(1) (R507.6.1). Connectors follow the manufacturer's specification with a zinc coating or hot-dipped galvanizing (Table R507.2.3), and joist ends need lateral restraint, such as hangers or blocking at least 60 percent of the joist depth (R507.6.2). Wood decking is fastened to each supporting joist with at least two 8d threaded nails or two No. 8 wood screws (R507.7), and Table R507.7 limits joist spacing by decking thickness. Any deck walking surface more than 30 inches above grade, at any point within 36 inches horizontally of its edge, needs a guard at least 36 inches high, with openings sized so a 4-inch sphere cannot pass through (R312.1.1 through R312.1.3), under the same IRC R312 guard provisions covered in more depth in Lesson 13 alongside stairways and handrails; a deck framing inspection is a natural point to flag a missing or undersized guard even before the life-safety lesson gets to it in detail.

Key numbers
  • Slab-on-ground minimum thickness: 3-1/2 in. (R506.1)
  • Below-grade slab base course: 4 in. clean graded material, waived on Group I soils (R506.2.2)
  • Slab vapor retarder: minimum 10 mil, ASTM E1745 Class A, laps ≥ 6 in., placed directly under the slab (R506.2.3)
  • Deck design load: 40 psf live load (Table R301.5) or ground snow load, whichever is greater (R507.1)
  • Ledger fasteners: 1/2 in. lag screws or bolts, hot-dipped galvanized or stainless, spaced per Table R507.9.1.3(1) (R507.9.1.3)
  • Deck lateral load connection: 2 hold-downs within 24 in. of the deck ends at 1,500 lb each minimum, or 4 at 750 lb each (R507.9.2)
  • Guard posts, 4x4 wood: no notch at the connection to the supporting structure (R507.10.2)
  • Guard height: 36 in. minimum where the walking surface is more than 30 in. above grade within 36 in. of the edge (R312.1)

In the field

A GCHS rehab crew is asked to shore up an older deck rather than replace it outright. The ledger bolts look adequate and the joists are sound, but there is no hardware anywhere connecting the deck framing back through the house rim joist, nothing but the ledger bolts themselves resisting the deck pulling away from the house. That is the lateral load connection missing, and it is invisible from a casual walk-around because there is nothing to see on the exterior face; it has to be checked by opening the rim joist area from inside, at the floor framing the deck ties into, or by asking whether it was ever installed in the first place on a deck built before that requirement was common practice.

Worked example. A deck post carries a beam with a tributary area (the deck surface the post carries) of 120 square feet, at an unbraced height of 7 feet from the underside of the beam to the top of the footing. At 40 psf live load, Table R507.4 gives a Douglas fir, hem-fir, or spruce-pine-fir 4x4 a limit of 7 feet at 120 square feet, so a 7-foot post is exactly at the limit, and a builder planning to go taller, or carry more area, fails the 4x4. At 140 square feet the 4x4 limit drops to 6 feet 2 inches, but a 4x6 is allowed 8 feet 7 inches. Interpolation between tributary areas is permitted and extrapolation is not, which is exactly the kind of boundary case the tables settle instead of a guess.

Deck load path from ledger to footing Elevation diagram of a deck attached to a house: a ledger bolted to the band joist with lag screws and flashed above, a lateral load hold-down device running from a deck joist through the rim joist to a house floor joist, a deck joist supported by a beam, the beam bearing on a post, and the post on a footing extending to frost depth. A guard at least 36 inches high is shown at the outer edge of the deck. House Ledger Flashing above ledger Deck joists Lateral hold-down 2 @ 1,500 lb min. Beam Post 4x4 or 6x6 Footing to frost depth Guard, 36 in. min.
Every link in this path is checked separately: ledger fasteners and flashing, a lateral connection independent of the ledger, joist hangers, post size for height and tributary area, and a footing to frost depth.

Practice questions

1. What is the minimum thickness of a concrete slab-on-ground floor under IRC R506.1?

  1. 2-1/2 inches
  2. 3 inches
  3. 3-1/2 inches
  4. 5 inches

2. A slab is placed below grade over ordinary soil that is not a well-drained Group I sand-gravel mix. R506.2.2 requires a base course beneath it of at least:

  1. 2 inches
  2. 4 inches
  3. 8 inches
  4. No base course is ever required below grade

3. Where is the required vapor retarder placed relative to the slab and base course, per R506.2.3?

  1. Directly beneath the concrete slab, above the base course or prepared subgrade
  2. Below the base course, directly on the compacted subgrade, with the gravel on top of it
  3. On top of the finished slab, under the floor finish, lapped 6 inches at the joints
  4. Only around the slab perimeter, turned up the foundation wall 6 inches

4. What live load do decks need to be designed for under R507.1, unless the ground snow load is greater?

  1. 20 psf
  2. 30 psf
  3. 50 psf
  4. 40 psf

5. Under R507.9.1.3, which fasteners may attach a deck ledger to the house band joist?

  1. 16d common nails toe-nailed at 12 inches on center along the ledger
  2. 1/2-inch lag screws or bolts, hot-dipped galvanized or stainless steel, spaced per Table R507.9.1.3(1)
  3. Construction adhesive plus 3-inch finish nails driven at each joist location
  4. Any fastener, provided the ledger does not move by hand

6. Under R507.9.1.1, a deck ledger may not be supported on which of the following?

  1. A solid-sawn spruce-pine-fir band joist at least 2 inches nominal thick
  2. An engineered wood rim board at least 1 inch nominal thick
  3. Stone or masonry veneer
  4. A band joist that bears fully on the primary structure

7. Why must a deck ledger be flashed (R507.2.4 and Table R507.9.1.3(1) note b)?

  1. To keep water from contacting the house band joist
  2. To improve the deck's appearance and hide the lag screw heads
  3. To add lateral strength to the connection between the ledger and the band joist
  4. Flashing is optional at ledger connections when the ledger is pressure-treated lumber

8. Where the lateral load connection follows Figure R507.9.2(1), R507.9.2 calls for hold-down tension devices in two locations, each with an allowable capacity of at least:

  1. 750 pounds each
  2. 1,500 pounds each
  3. 3,000 pounds each
  4. 500 pounds each

9. Why is the deck lateral load connection easy to miss during a casual walk-around inspection?

  1. It is always painted the same color as the siding
  2. It is only required on decks over 200 square feet
  3. It is visible only at night
  4. It runs through the house rim joist to an interior floor joist, so little shows outside

10. Under R507.10.2, a 4-inch by 4-inch wood post that supports guard loads applied to the top of the guard:

  1. Shall not be notched at the connection to the supporting structure
  2. May be notched up to one-half of its width where the guard rail is bolted through
  3. May be notched to one-third of its thickness if the notch is filled with adhesive
  4. May be notched only on the outside face, if a metal saddle connector is added

11. Per Table R507.4 at 40 psf live load, compared with a 4x4, a 6x6 deck post at the same tributary area allows:

  1. A shorter maximum post height, because it has more wood to buckle
  2. The same maximum post height at every tributary area, regardless of species
  3. Use only in commercial construction
  4. A taller maximum post height at the same tributary area, up to the table's 14-foot cap

12. Where deck joists frame into the side of a ledger or beam, R507.6.1 requires them to be supported by:

  1. A notch cut into the ledger so each joist end rests on the reduced section
  2. Approved joist hangers
  3. Toenails driven through each joist end into the face of the beam
  4. Construction adhesive applied along the full length of the joist end

13. A deck's walking surface is more than 30 inches above grade within 36 inches of its edge. Under R312.1, the required guard along the open side must be at least:

  1. 30 inches high, with openings that do not pass a 4-inch sphere
  2. 42 inches high, with openings that do not pass a 6-inch sphere
  3. 36 inches high, with openings that do not pass a 4-inch sphere
  4. 34 inches high, with openings that do not pass a 4-3/8-inch sphere

14. Where a vapor retarder would otherwise be required under a slab, which of the following is a typical exception?

  1. An unheated detached garage or utility building slab
  2. A heated living room slab covered with a floating laminate floor
  3. A slab under a finished basement family room that is heated and carpeted
  4. A slab under a bedroom addition built on a gravel base course

Glossary

Vapor retarder
A membrane of at least 10 mil under the 2021 IRC, placed directly beneath a concrete slab to block ground moisture.
Ledger
The horizontal member bolted to a house's band joist that carries the inner end of a deck's joists.
Lateral load connection
A hold-down device connecting deck framing through the house rim joist to a floor joist, resisting the deck pulling away from the house.
Tributary area
The floor or roof area whose load a given post, beam, or footing is assumed to carry, used to size that member.
Guard
A protective barrier at an open-sided walking surface, required at 36 inches minimum once the surface is more than 30 inches above grade within 36 inches of the edge.
DCA 6
The American Wood Council's Prescriptive Residential Wood Deck Construction Guide, restating the IRC's deck provisions in lookup tables and details.
Group I soil
A well-drained sand-gravel soil classification under the Unified Soil Classification System, exempted from certain base-course requirements.